7. Operation

7. Operation

7.1 Backlight

When either of the 7.1 Backlight7.2 Displaying and Setting the Temperature buttons is pressed, the display is lit for 10 seconds. The setpoint appears for 5 seconds, then the actual tem- perature is displayed.

When the backlight button is pressed, the display is lit for 5 sec- onds. NOTE: If the thermostat is mounted on a GFCI-equipped power base, this button is used for the GFCI test.

7.2 Displaying and Setting the Temperature

The thermostat normally displays the actual temperature. To view

the setpoint, press once on one of the 7.3 Setting the Floor Temperature Limits (AF model only)8. Techn ical Specifications buttons. The setpoint is displayed for 5 seconds. During the setpoint display, press one of

the Ambient setpoint range (A/AF models): 5°C to 30°C (40°F - 86°F)Floor limit range (AF model): 5°C to 40°C (40°F - 104°F) buttons to change it. To scroll the setpoint faster, press and hold the button.

7.3 Setting the Floor Temperature Limits (AF model only)

The thermostat generally turns heating On or Off to con- trol the ambient temperature. However, if the floor tem- perature drops below the set minimum floor temperature limit or rises above the maximum limit, the thermostat will turn heating On or Off respectively, regardless of the ambient temperature, to maintain the floor temperature within the desired limits.

The minimum and maximum floor temperature limits are factory-set at 10°C (50°F) and 28°C (82°F) respectively. To modify the limits, proceed as follows:

nSwitch the thermostat to Standby.

oWhile pressing any button, switch the thermostat back to On to access the floor temperature limit settings.

pPress the Test button briefly to switch between minimum and maximum floor temperature settings.

qPress the Floor setpoint range (F model): 5°C to 40°C (40°F - 104°F)Setpoint resolution: ± 0.5°C (1.0°F) buttons to set the desired limit.

rPress the Test button for 3 seconds to save your modifications. After the data are saved, the thermostat displays the actual ambient temperature or “– –”.

Note: Your modifications are also saved if no button is pressed for 60 seconds.

sSwitch the thermostat to Standby and back to On to reset the

GFCI and return to the normal display.

:

8. Techn ical Specifications

Power supply: Refer to the power base installation instructions.

Ambient setpoint range (A/AF models): 5°C to 30°C (40°F - 86°F)

Floor limit range (AF model): 5°C to 40°C (40°F - 104°F)

Floor setpoint range (F model): 5°C to 40°C (40°F - 104°F)

Setpoint resolution: ± 0.5°C (1.0°F)

Display resolution: ± 0.5°C (1.0°F)

Duty cycle: Refer to the power base installation instructions.

Storage: -20°C to 50°C (-4°F - 120°F)

9. Warranty

AUBE TECHNOLOGIES INC. ONE (1) YEAR LIMITED WARRANTY

This product is guaranteed against workmanship defects for a one year period following the initial date of purchase. During this period, AUBE Technologies Inc. will repair or replace, at our option and without charge, any defective product which has been used under normal conditions.

The warranty does not cover delivery costs and does not apply to products poorly installed or randomly damaged following installa- tion. This warranty cancels and replaces any other manufacturer's express or implied warranty as well as any other company commit- ment.

AUBE Technologies Inc. cannot be held liable for related or random damages following the installation of this product. The defective product as well as the purchase invoice must be returned to the place of purchase or mailed, prepaid and insured, to the following address.

1 0. Service

705 Montrichard

Saint-Jean-sur-Richelieu, Quebec

J2X 5K8

Canada

T: (450) 358-4600

1-800-831-AUBE (2823)

F:(450) 358-4650 service@aubetech.com

For more information on our products, visit us at:

www.aubetech.com

TH114

400-114-000-B

21/2/05

2/2

Page 2
Image 2
Aube Technologies TH114 installation instructions Operation, Techn ical Specifications, Warranty, 1 0. Service, Backlight