CHECKING

M3LDY

CHECKING

1)Terminal wiring: Check that all cables are correctly connected according to the connection diagram.

2)DIP SW setting: Check that the switches are set to appropriate positions.

3)Power input voltage: Check voltage across the terminal 11 Ð 12 with a multimeter.

4)Input: Check that the input signal is within 0 Ð 100% of full-scale.

5)Output: Check that the load resistance meets the described specifications.

I/O RANGING & FINE ADJUSTMENTS

After the DIP SW setting is complete, set up the precise input and output range using the front control buttons.

The front LEDsÕ colors and flashing patterns help you to easily identify the transmitterÕs status and confirm the setup actions in each step of Calibration Modes. Please read the following explanations referring to ÒCalibration Flow ChartÓ below.

CALIBRATION FLOW CHART

POWER ON

LD1

G

MODE

UP

Control

A Amber LED

OFF

G Green LED ON

Fine Adjustments ?

LD2

RUN MODE

 

 

 

LD3

 

 

G

 

I/O Ranging ?

DOWN

Buttons

R Red LED

Blink

PUSH

MODE

1 – 2 s

PRESS & HOLD

MODE

> 5s

Apply simulated 0% input signal.

LD1

RFINE ZERO

LD2

CALIBRATION MODE

G

 

*1

LD1

 

R

INPUT

LD2

 

RCALIBRATION

PUSH

 

 

 

 

0% INPUT

DOWN

 

 

 

 

 

 

CONFIGURED

 

 

 

 

 

 

 

 

 

 

 

LD3

UP

or DOWN

 

LD3

MODE

PUSH

 

 

 

100% INPUT

UP

 

 

 

 

CONFIGURED

 

 

 

 

Apply simulated 100% input signal.

PUSH MODE

PUSH MODE

Adjust simulated input until the output meter shows desired 0% output.

LD1

R

LD2

LD3

G

FINE SPAN

CALIBRATION MODE

UP or DOWN

*1

LD1

R

LD2

LD3

R

OUTPUT

CALIBRATION

MODE

PUSH DOWN

PUSH UP

0% OUTPUT

CONFIGURED

100% OUTPUT CONFIGURED

PUSH

MODE

LD1

G

LD2

LD3

RUN MODE

PUSH

Adjust simulated input until the output meter shows desired 100% output.

MODE

When you set 0% or 100% input/output ranges, keep pressing UP or DOWN button until the LD1 flashes for approx. 2 seconds and turns off, which indicates the setup is complete.

When you release the button, the LD1 is returned to ON.

If the LED does not change, the entered level may be inappropriate, i.e. out of usable range.

*1. Fine zero and calibrations are performed for 0% and 100% output regardless of the input value.