Modbus Basics been lost. Lost communication is indicated by the Bus LED’s blinking alternately. The default value of 10 is usually satisfactory. The range of values is 10 to 255.
To configure the Zlinx 485 Base Module for
1.Select the Configuration tab.
2.Select the
3.Set the
Figure 33. Peer-to-Peer Slave Configuration
Input/Output Settings
Digital inputs and analog inputs/outputs on Zlinx 485 modules are configured from the Input/Output tab of the Zlinx 485 Manager. The first two digital inputs on any module can be configured as Discrete inputs or Frequency Counter inputs. (Any additional digital inputs operate as Discrete inputs only.) Frequency Counter operation is only functional when the Zlinx 485 is set up in Modbus mode. Analog inputs and outputs can be configured for voltage or current loop operation.
To configure digital and analog I/O:
1. Select the Input/Output tab.
Manual Documentation Number: