Bard EIFM-5C installation instructions TOP View Blower Partition

Models: EIFM-5C

1 12
Download 12 pages 38.97 Kb
Page 5
Image 5

IMPORTANT: Position front lip of economizer on top of front grille and condenser partition (See Figure 2 inset.) This is important to ensure proper drainage of any water entering damper assembly.

LEFT HAND UNITS Slide the economizer to the left until it is tight against the back of the corner panel.

6.Mount mixed air thermistor to blower partition with screws provided. Bracket with sensor installs on top of blower partition and screws are installed from the underside. Route wires as shown and secure with wire tie. Connect wires to thermistor. (See Figure 2.)

7.Open unit control panel to gain access to unit low voltage terminal block.

8.FOR LEFT HAND UNITS – Reroute economizer wiring harness to the left side of the economizer. (See Figure 3.)

9.Route electrical harness leads through the 7/8" bushing in control panel (Figure 2) into low voltage box.

FIGURE 2

TOP VIEW OF

BLOWER PARTITION

THERMISTOR

PART #8602-043

THERMISTOR BRACKET PART #113-264

 

INSTALL THERMISTOR TO

 

BLOWER PARTITION. ROUTE

 

WIRES FROM ECONOMIZER

 

BEHIND FILTER BRACKET FILL

 

& THROUGH WIRE TIE.

 

WIRE TIE TO SUCTION LINE

 

LOW VOLTAGE WIRES TO

 

TERMINAL STRIP

MIST ELIMINATOR

WHEN INSTALLING ECONOMIZER, POSITION SO THAT HOLE

 

IN FRONT LIP IS CENTERED OVER HOLE IN CONDENSER

 

GRILLE TO INSERT A SELF DRILLING SCREW

SIDE SECTION

RIGHT SIDE OF ECONOMIZER

SERVICE DOOR

LIP OF ECONOMIZER IS TO BE BETWEEN THE CONDENSER GRILLE AND SERVICE DOOR

THERMISTOR WIRES

CONDENSER PARTITION

FRONT GRILLE

MIS-423

Manual 2100-447 Page 3

Page 5
Image 5
Bard EIFM-5C installation instructions TOP View Blower Partition