COOLING PRESSURE

TABLE 12

j

 

COOLING PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Temperature °F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Return Air

 

 

 

 

 

 

 

 

 

 

 

 

Model

Temperature

Pressure

75

80

85

90

95

100

105

 

110

115

 

 

75 deg DB

Low Side

75

76

78

79

80

81

83

 

84

85

 

 

62 deg WB

High Side

215

229

244

258

275

292

308

 

327

345

 

WA302

80 deg DB

Low Side

80

81

83

85

86

87

89

 

90

91

 

67 deg WB

High Side

220

235

250

265

282

299

316

 

335

354

 

 

 

 

 

85 deg DB

Low Side

83

84

86

88

89

90

92

 

93

94

 

 

72 deg WB

High Side

228

243

259

274

292

309

327

 

347

366

 

 

75 deg DB

Low Side

69

70

72

74

75

77

78

 

79

79

 

 

62 deg WB

High Side

200

214

229

245

261

279

296

 

316

335

 

WA372

80 deg DB

Low Side

75

75

77

79

80

82

83

 

84

85

 

67 deg WB

High Side

205

219

235

251

268

286

304

 

324

344

 

 

 

 

 

85 deg DB

Low Side

77

78

80

82

83

85

86

 

87

88

 

 

72 deg WB

High Side

212

227

243

260

277

298

315

 

335

358

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low side pressure ± 2 psig

High side pressure ± 5 psig

Tables are based upon rated CFM (airflow) across the evaporator coil and should be found under section titled "Refrigerant Charge" elsewhere in manual. If there is any doubt as to correct charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instructions.