Bard MIS-656 installation instructions Wiring - Low Voltage Wiring, Table Operating Voltage Range

Models: MIS-656

1 19
Download 19 pages 30.09 Kb
Page 9
Image 9
WIRING — LOW VOLTAGE WIRING

The electrical data lists fuse and wire sizes (75ºC copper) for all models, including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR Type” circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut, a padlock may be placed through the hole in the tab preventing entry.

WIRING — LOW VOLTAGE WIRING

230/208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TABLE 4

OPERATING VOLTAGE RANGE

TAP

RANGE

240V

253 – 216

208V

220 – 187

 

 

NOTE: The voltage should be measured a the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition.)

Five (5) wires should be run from thermostat subbase to the 24V terminal board in the unit. A five conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 10.

TABLE 5

THERMOSTAT WIRE SIZE

 

 

 

Maximum

Transformer

 

 

Distance

VA

FLA

Wire Gauge

In Feet

 

 

20 gauge

45

 

 

18 gauge

60

55

2.3

16 gauge

100

 

 

14 gauge

160

 

 

12 gauge

250

TABLE 6

WALL THERMOSTAT AND SUBBASE COMBINATIONS

Thermostat

Subbase

Predominate Features

 

 

 

8403-002

8404-003

1 stage heat, 1 stage cool

T87F3111

Q539A1220

System: heat-off-cool

Fan: auto-on

 

 

 

8403-041

---

1 stage heat, 1 stage cool

T8034C

System: heat-off-cool

Fan: auto-on

 

8403-019

8404-012

1 stage cool, 2 stage heat

T874C1760

Q674A1001

System: heat-auto-cool

Fan: auto-on

 

 

 

8403-021

8404-012

2 stage cool, 2 stage heat

T874D1934

Q674A1001

System: heat-auto-cool

Fan: auto-on

8403-049

---

2 stage cool, 2 stage heat

1F93-380

Electronic 7 day programming w/ventilation control

 

 

 

 

8403-043

---

1 stage heat, 1 stage cool

CM-200

System: heat-off-cool

Fan: auto-on

 

Manual 2100-404 Page 7

Page 9
Image 9
Bard MIS-656 Wiring - Low Voltage Wiring, Table Operating Voltage Range, Table Thermostat Wire Size