QC SERIES WATER SOURCE GENERAL INFORMATION
QC MODEL NOMENCLATURE
QC 50 1 – A
10 | X | X | X | X | X | X | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Filter Options |
|
|
|
|
|
| |
|
|
|
|
|
| Valve Options |
| |||
KW |
| X - 1 Inch Fiberglass |
|
|
Model Number
QC - QTec™ Model
Capacity 50 - 4 ton
Revision
Volts & Phase A -
0Z - 0KW | (Standard) | 4 - | |||||||
05 - 5 KW | F - 2 Inch Fiberglass | 5 - | |||||||
10 - 10KW | P - 2 Inch pleated |
|
|
|
|
| |||
15 - 15KW |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Internal Controls | |||
(Note 1) |
|
|
|
|
|
| |||
|
|
|
|
|
| X - None | |||
Color |
|
| |||||||
|
|
| |||||||
| V - Platinum w/Slate |
|
|
|
|
| |||
| Front (vinyl) |
|
|
|
|
| |||
| 4 - Gray Paint |
|
|
|
|
| |||
| Climate Control | ||||||||
|
|
|
|
| |||||
Ventilation Option |
|
|
|
| X - None | ||||
B - Blank Off Plate (no ventilation) | D - Electronic/prog/man/auto |
X - Barometric Fresh Air Damper (no exhaust)
V - Commercial Ventilator (w/Exhaust)
NOTE 1: Electric heat available for
P - Commercial Ventilator (w/Exhaust)
Motorized, Power Return
R - Energy Recovery Ventilator (w/Exhaust) -
TABLE 1
FACTORY
Models |
| ||
|
|
|
|
|
| ||
|
|
|
|
KW | BTUH |
| BTUH |
5.0 | 16,380 |
| 12,290 |
|
|
|
|
10.0 | 32,670 |
| 24,570 |
15.0 | 49,150 |
| 36,860 |
|
|
|
|
TABLE 2
ELECTRICAL SPECIFICATIONS
Single Circuit | Dual Circuit |
|
|
| 3 | 1 | 2 | 2 |
| 3 |
| 1 |
| 2 |
| 2 | ||||
|
|
|
|
|
|
|
|
|
| Maximum |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| External |
|
|
|
|
|
| ||
|
| No. |
| Maximum |
|
| Minimum | Fuse or | Field |
|
|
| ||||||
|
|
| External | Field |
| Circuit | Circuit | Power | Ground | |||||||||
| Rated | Field | Minimum | Fuse or | Power | Ground | Ampacity | Breaker | Wire Size | Wire Size | ||||||||
| Volts & | Power | Circuit | Circuit | Wire | Wire |
|
|
|
|
|
|
|
|
|
|
|
|
| CKT | CKT | CKT | CKT | CKT | CKT | CKT | CKT | ||||||||||
| Phases | Circuits | Ampacity | Breaker | Size | Size | ||||||||||||
Models | A |
| B | A |
| B | A |
| B | A |
| B | ||||||
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1 | 7 | 15 | 14 | 14 | – |
| – | – |
| – | – |
| – | – |
| – | |
1 | 33 | 35 | 8 | 10 | – |
| – | – |
| – | – |
| – | – |
| – | ||
1 | 58 | 60 | 6 | 10 | – |
| – | – |
| – | – |
| – | – |
| – | ||
| 1 or 2 | 83 | 90 | 4 | 8 | 50 |
| 33 | 50 |
| 40 | 8 |
| 8 | 10 |
| 10 | |
1 | 10 | 15 | 14 | 14 | – |
| – | – |
| – | – |
| – | – |
| – | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
QMaximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
RBased on 75° C copper wire. All wiring must conform to the National Electrical Code and all local codes.
SThese “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National
Electric Code (latest revision), article 310 for power conductor sizing. CAUTION: When more than one field
power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.
Manual
Page 2