Bard QC501 Troubleshooting Ecm Blower Motors, Symptom, Motor rocks slightly when starting, Dont

Models: QC501

1 27
Download 27 pages 36.78 Kb
Page 24
Image 24
TROUBLESHOOTING ECM BLOWER MOTORS

TROUBLESHOOTING ECM BLOWER MOTORS

SYMPTOM CAUTION

Disconnect power from unit before removing or replacing connectors, or servicing motor. Wait at least 5 minutes after disconnection power before opening motor.

SYMPTOM

Motor rocks slightly when starting.

Motor won't start

%No movement

%Motor rocks, but wo'nt start

Motor oscillates up and down while being tested off of blower

%Noisy blower of cabinet

%"Hunts" or "puffs" at high CFM (speed)

Evidence of Moisture

CAUSE / PROCEDURE

%This is normal start-up for ICM

%Check power at motor

%Check low voltage (24 VAC R to C) at motor

%Check low voltage connections (G, Y, W, R, C) at motor

%Check for unseated pins in connectors on motor harness

%Test with a temporary jumper between R - G

%Check motor for tight shaft

%Run Mositure Check

%Check for loose or compliant motor mount

%Make sure blower wheel is tight on shaft

%It is normal for motor to oscillate with no load on shaft.

%Check for loose blower housing, panels, etc.

%High static creating high blower speed?

Check for air whistling through seams in ducts, cabinets or panels.

Check for cabinet / duct deformation

%Does removing panel or filter reduce "puffing"?

Reduce restiction

Reduce maximum airflow

% Motor failure of malfunction has occured and

%

Replace motor and perform Moisture Check

%

moisture is present

%

Perform Moisture Check

Evidence of moisture present inside air mover

DO

 

DON'T

%

Check out motor, controls, wiring and connections

%

Automatically assume the motor is bad

 

thoroughly before replacing motor

 

 

%

Orient connectors down so water ca'nt get in;

% Locate connectors above 7 and 4 o'closk postions

install "drip loops"

%Use authorized motor and control model numbers % Replace one motor of control model number with another

for replacement

 

(unless an authorized replacement)

% Keep static pressure to a minimum:

%

Use high pressure drop filters. Some have 1/2" H O drop!

 

 

2

– Recommend high efficiency, low static filters

%

Use restricted returns

Recommend keeping filters clean

Design duct work for minimum static, maximum comfort

Look for and recommend duct work improvement,where necessary, in replacement.

Manual 2100-416

Page 22

Page 24
Image 24
Bard QC501 Troubleshooting Ecm Blower Motors, Symptom, Motor rocks slightly when starting, Motor wont start, Dont