TABLE 7
PRESSURE TABLE
COOLING |
|
|
|
| Air Temperature Entering Outdoor Coil °F |
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| |
Model | Return Air | Pressure | 75° | 80° | 85° | 90° | 95° | 100° | 105° | 100° | 115° | |
Temperature | ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
| 75 deg. DB | Low Side | 120 | 124 | 129 | 133 | 136 | 138 | 141 | 142 | 143 | |
| 62 deg. WB | High Side | 291 | 310 | 332 | 355 | 379 | 405 | 432 | 460 | 490 | |
W12Aà | 80 deg. DB | Low Side | 128 | 133 | 138 | 142 | 143 | 148 | 151 | 152 | 153 | |
67 deg. WB | High Side | 298 | 318 | 340 | 364 | 387 | 415 | 443 | 472 | 503 | ||
| ||||||||||||
| 85 deg. DB | Low Side | 132 | 138 | 143 | 147 | 150 | 153 | 156 | 157 | 158 | |
| 72 deg. WB | High Side | 308 | 329 | 352 | 377 | 403 | 430 | 459 | 489 | 521 |
Low Side Pressure +4 PSIG
High Side Pressure +10 PSIG
TABLE 8
OPTIONAL FIELD INSTALLED ACCESSORIES
ModelDescription
W12Aà
Blank Off Plate | X | |
Barometric Fresh Air Damper | X | |
Economizer with Exhaust | X | |
|
|
|
Low Ambient Control | X | |
|
|
|
Commercial Ventilator - Spring Return | X | |
|
|
|