TROUBLESHOOTING
FAN BLADE SETTING DIMENSIONS
Shown in Figure 7 is the correct fan blade setting dimension for proper air delivery across the outdoor coil.
Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimension below be checked and blade adjusted in or out on the motor shaft accordingly.
FIGURE 7
FAN BLADE SETTING DIMENSION
TABLE 4
INDOOR BLOWER
PERFORMANCE
CFM @ 230V / 115V
E.S.P. |
|
| W12Aà |
| |
| 230V / 115V |
| |||
in |
|
| |||
H2O | Dry / Wet |
| Dry / Wet | ||
| High |
| Low | ||
.0 | 530 | / 500 |
| 465 | / 425 |
.1 | 485 | / 460 |
| 415 | / 400 |
.2 | 440 | / 425 |
| 365 | / 350 |
.3 | 390 | / 375 |
| 315 | / 300 |
.4 | 325 | / 300 |
| 270 | / 265 |
TABLE 5
RATED CFM AND ESP
RECOMMENDED AIRFLOW RANGE
Model | ° | ° | Recommended | |
Rated | Rated | |||
Airflow Range | ||||
| CFM | ESP | ||
|
| |||
|
|
|
| |
W12Aà | 400 | .10 | 500 - 300 |
°Rated CFM and ESP on low speed tap.
TABLE 3
FAN BLADE DIMENSION
Model | Dimension A |
|
|
W12Aà | 1/2" |
R-410A
REFRIGERANT CHARGE
This unit was charged at the factory with the quantity of refrigerant listed on the serial plate. AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity.
The following pressure tables show nominal pressures for the units. Since many installation specific situations can affect the pressure readings, this information should only be used by certified technicians as a guide for evaluating proper system performance. They shall not be used to adjust charge. If charge is in doubt, reclaim, evacuate and recharge the unit to the serial plate charge.
TABLE 6
MAXIMUM ESP OF OPERATION
ELECTRIC HEAT ONLY
Model | ESP |
.35 | |
A03 | .35 |
A05 | .35 |
.35 | |
K02 | .35 |
Values shown are for units equipped with STD 1" throwaway filters. Derate ESP by .15 for 2" pleated filters.