TROUBLESHOOTING

TROUBLESHOOTING

FAN BLADE SETTING DIMENSIONS

Shown in Figure 7 is the correct fan blade setting dimension for proper air delivery across the outdoor coil.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimension below be checked and blade adjusted in or out on the motor shaft accordingly.

FIGURE 7

FAN BLADE SETTING DIMENSION

TABLE 4

INDOOR BLOWER

PERFORMANCE

CFM @ 230V / 115V

E.S.P.

 

 

W12Aà

 

 

230V / 115V

 

in

 

 

H2O

Dry / Wet

 

Dry / Wet

 

High

 

Low

.0

530

/ 500

 

465

/ 425

.1

485

/ 460

 

415

/ 400

.2

440

/ 425

 

365

/ 350

.3

390

/ 375

 

315

/ 300

.4

325

/ 300

 

270

/ 265

TABLE 5

RATED CFM AND ESP

RECOMMENDED AIRFLOW RANGE

Model

°

°

Recommended

Rated

Rated

Airflow Range

 

CFM

ESP

 

 

 

 

 

 

W12Aà

400

.10

500 - 300

°Rated CFM and ESP on low speed tap.

TABLE 3

FAN BLADE DIMENSION

Model

Dimension A

 

 

W12Aà

1/2"

R-410A

REFRIGERANT CHARGE

This unit was charged at the factory with the quantity of refrigerant listed on the serial plate. AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity.

The following pressure tables show nominal pressures for the units. Since many installation specific situations can affect the pressure readings, this information should only be used by certified technicians as a guide for evaluating proper system performance. They shall not be used to adjust charge. If charge is in doubt, reclaim, evacuate and recharge the unit to the serial plate charge.

TABLE 6

MAXIMUM ESP OF OPERATION

ELECTRIC HEAT ONLY

Model

ESP

W12A2-A00

.35

A03

.35

A05

.35

W12A1-K00

.35

K02

.35

Values shown are for units equipped with STD 1" throwaway filters. Derate ESP by .15 for 2" pleated filters.