ADJUSTMENTS
Adjustable Delay on Make and Delay on Break Timer
The potentiometer is used to select Delay on Break time from 30 seconds to 5 minutes. Delay of Make (DOM) timing on power up and after power interruptions is equal to 2 minutes plus 10% of Delay of Break (DOB) setting:
0.5 minute (30 seconds) | DOB = 123 second | DOM |
1.0 minute (60 seconds) | DOB = 126 second | DOM |
2.0minute (120 seconds) DOB = 132 second DOM
3.0minute (180 seconds) DOB = 138 second DOM
4.0minute (240 seconds) DOB = 144 second DOM
5.0minute (300 seconds) DOB = 150 second DOM
During routine operation of the unit with no power interruptions the compressor will operate on demand with not delay.
Typical Settings for Dual Unit Installation:
Unit No. 1: DOB set at 2 minutes, and DOM is 132 seconds.
Unit No. 2: DOB set at 4 minutes, and DOM is 144 seconds.
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure chart can be found later in the manual covering all models. It is imperative to match the correct pressure chart to the unit by model number.