iEM3100 / iEM3200 / iEM3300 series user manual

Front panel display and meter setup

 

 

Configuration menus for iEM3200 / iEM3210 / iEM3215

Wiring

CT Ratio

Frequency

Date

Time

Pulse Output

Multi Tariffs

Contrast

Password

Reset Config

Type

CT

CT Secondary

CT Primary

Frequency

Date

Time

Pulse Constant

Pulse Width

Control mode

 

 

Disable

 

 

by Internal Clock

 

Schedule

 

by Digital Input

 

by 2 Tariffs

by Communications

 

by 3 Tariffs

 

 

by 4 Tariffs

Contrast

 

 

Password

 

 

Reset Config

 

 

AiEM3210 / iEM3215

BiEM3210

CiEM3215

Section

Parameter

Options

Description

 

 

 

 

 

 

3PH3W

 

 

 

3PH4W

 

 

Type

1PH2W L-N

Select the power system type the meter is wired to.

Wiring

 

1PH2W L-L

 

 

1PH3W L-L-N

 

 

 

 

 

 

 

 

 

 

3CTs on I1, I2, I3

Define how many current transformers (CT) are connected to the meter and

 

CT

1 CT on I1

 

which terminals they are connected to.

 

 

2 CTs on I1, I3

 

 

 

 

 

 

 

 

CT Secondary

1

Select the size of the CT secondary, in Amps.

CT Ratio

5

 

 

 

CT Primary

1 - 32767

Enter the size of the CT primary, in Amps.

 

 

 

 

Frequency

Frequency

50

Select the frequency of the electrical power system, in Hz.

60

 

 

 

 

 

 

 

Date (iEM3210 / iEM3215)

Date

DD-MMM-YYYY

Set the current date using the specified format.

 

 

 

 

Time (iEM3210 / iEM3215)

Time

hh:mm

Set the time using the 24-hour format.

 

 

 

 

 

 

0.01

 

 

 

0.1

 

 

Pulse Constant

1

Set the pulses per kWh for the pulse output.

 

(imp/kWh)

10

 

 

Pulse Output (iEM3210)

 

100

 

 

500

 

 

 

 

 

 

 

 

 

 

50

 

 

Pulse Width

100

Set the pulse width (ON time).

 

(ms)

200

 

 

 

 

300

 

 

 

 

 

DOCA0005EN-04

45

Page 45
Image 45
Schneider Electric iEM3300, iEM3100 user manual Configuration menus for iEM3200 / iEM3210 / iEM3215