TroubleshootingiEM3100 / iEM3200 / iEM3300 series user manual

Diagnostic codes

If the diagnostics code persists after following the instructions below, please contact Technical

Support.

Diagnostic code1

Description

Possible solution

LCD display is not visible.

Check and adjust LCD contrast.

 

 

 

Push buttons do not respond.

Restart the meter by powering off and powering on again.

 

 

 

101

Metering stops due to an EEPROM error.

Enter configuration mode and select Reset Config.

Press OK to display total energy consumption.

 

 

102

Metering stops due to a lack of a calibration table.

Enter configuration mode and select Reset Config.

Press OK to display total energy consumption.

 

 

 

Metering continues.

Correct the frequency settings according to the nominal frequency of

201

Mismatch between frequency settings and frequency

the power system.

 

measurements.

 

202

Metering continues.

Correct the wiring settings according to wiring inputs.

Mismatch between wiring settings and wiring inputs.

 

 

 

 

 

203

Metering continues.

Check the wire connections and correct the wiring settings if needed.

Phase sequence reversed.

 

 

 

Metering continues.

 

204

Total active energy is negative due to incorrect voltage and

Check the wire connections and correct the wiring settings if needed.

 

current connections.

 

205

Metering continues.

Set the Date and Time.

Date and Time have been reset due to a loss of power.

 

 

 

 

 

206

Metering continues.

Check the energy pulse output settings and correct if needed.

Pulse is missing due to overload on energy pulse output.

 

 

 

 

 

207

Metering continues.

Restart the meter by powering off and powering on again then reset the

Abnormal internal clock function.

date and time.

 

1 Not all diagnostic codes apply to all devices.

104

DOCA0005EN-04

Page 104
Image 104
Schneider Electric iEM3100, iEM3300, iEM3200 user manual Diagnostic codes, Description Possible solution