Hardware and installation

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

Input, output and communications wiring

This section describes the wiring of the digital inputs, digital and pulse outputs and the communications (as applicable).

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E in the USA or applicable local standards.

This equipment must only be installed and serviced by qualified electrical personnel.

Turn off all power supplying this device and the equipment in which it is installed before working on the device or equipment.

Always use a properly rated voltage sensing device to confirm power is off.

Replace all devices, doors and covers before turning on power to this equipment.

Do not exceed the device’s ratings for maximum limits.

Failure to follow these instructions will result in death or serious injury.

WARNING

UNINTENDED OPERATION

Do not use the meter for critical control or protection applications where human or equipment safety relies on the operation of the control circuit.

Failure to follow these instructions can result in death, serious injury or equipment damage.

Related topics

See “Power system wiring” on page 26 for information on wiring the voltage and current connections.

Pulse output wiring: iEM3110 / iEM3210 / iEM3310

 

Rin

 

Radd

5 – 30 V DC

+

-

 

S0+ S0-

The pulse output is compatible with S0 format.

The pulse output can be directly connected to a 24 V DC (< 30 V DC) input on a Zelio or Twido PLC.

The pulse output indicates the primary consumption with consideration of transformer ratios.

For other concentrators, if V DC/Rin > 15 mA, add a resistor Radd = (V DC/0.01) - Rin Ω

Digital input wiring: iEM3115 / iEM3215

11 – 40 V DC

- +

 

C/- T1

T2

24

DOCA0005EN-04

Page 24