Schneider Electric iEM3300, iEM3200, iEM3100 user manual Energy, energy by tariff and input metering

Models: iEM3100 iEM3200 iEM3300

1 112
Download 112 pages 230 b
Page 60
Image 60
Energy, energy by tariff and input metering

Communications via Modbus RS-485

 

 

 

 

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Register

Action

Size

Type

Units

Description

 

Address

(R/W/WC)

 

 

 

 

 

 

 

 

Power Factor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total Power Factor:

 

 

 

 

 

 

-2 < PF < -1 = Quad 2, active power negative, capacitive

 

3084

R

2

Float32

-1 < PF < 0 = Quad 3, active power negative, inductive

 

 

 

 

 

 

0 < PF < 1 = Quad 1, active power positive, inductive

 

 

 

 

 

 

1 < PF < 2 = Quad 4, active power positive, capacitive

 

 

 

 

 

 

 

 

Frequency

 

 

 

 

 

 

 

 

 

 

 

 

3110

R

2

Float32

Hz

Frequency

Energy, energy by tariff and input metering

Most energy values are available in both signed 64-bit integer and 32-bit floating point format. The energy and energy by tariff measurements listed below are preserved through power failures.

Energy reset and active tariff information

Register

Action

Size

Type

Units

Description

Address

(R/W/WC)

 

 

 

 

 

 

3252

R

4

DATETIME

Energy Reset Date and Time

 

 

 

 

 

 

3554

R

4

DATETIME

Input Metering Accumulation Reset Date and Time

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

 

 

 

MultiTariffs Energy Active Rate

 

 

 

 

 

0: multi tariff disabled

4191

R/WC

1

UInt16

1 to 4: rate A to rate D

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

 

 

 

NOTE: You can only set the tariff using this method if the Tariff Mode

 

 

 

 

 

is set to by Communication.

Energy values – 64-bit integer

Register

Action

Size

Type

Units

Description

Address

(R/W/WC)

 

 

 

 

 

 

Total Energy (cannot be reset)

 

 

 

 

 

 

 

 

3204

R

4

Int64

Wh

Total Active Energy Import

3208

R

4

Int64

Wh

Total Active Energy Export

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

 

 

 

 

3220

R

4

Int64

VARh

Total Reactive Energy Import

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

 

 

 

 

3224

R

4

Int64

VARh

Total Reactive Energy Export

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

Partial Energy

 

 

 

 

 

 

 

 

 

 

3256

R

4

Int64

Wh

Partial Active Energy Import

 

 

 

 

 

 

3272

R

4

Int64

VARh

Partial Reactive Energy Import

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

Phase Energy

 

 

 

 

 

 

 

 

 

 

3518

R

4

Int64

Wh

Active Energy Import Phase 1

 

 

 

 

 

 

3522

R

4

Int64

Wh

Active Energy Import Phase 2

 

 

 

 

 

 

3526

R

4

Int64

Wh

Active Energy Import Phase 3

 

 

 

 

 

 

Input Metering Counter

 

 

 

 

 

 

 

 

 

3558

R

4

Int64

Unit

Input Metering Accumulation

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

 

 

 

 

Energy by Tariff (iEM3155 / iEM3255 / iEM3355 only)

 

 

 

 

 

 

4196

R

4

Int64

Wh

Rate A Active Energy Import

 

 

 

 

 

 

4200

R

4

Int64

Wh

Rate B Active Energy Import

 

 

 

 

 

 

4204

R

4

Int64

Wh

Rate C Active Energy Import

 

 

 

 

 

 

4208

R

4

Int64

Wh

Rate D Active Energy Import

 

 

 

 

 

 

60

DOCA0005EN-04

Page 60
Image 60
Schneider Electric iEM3300, iEM3200, iEM3100 user manual Energy, energy by tariff and input metering