Power and PF lead / lag

iEM3100 / iEM3200 / iEM3300 series user manual

Power, energy and power factor

 

 

Power and PF lead / lag

+Q

(+kVAR)

Quadrant 2

Quadrant 1

Q (+)

PF lead

-P (-kW)

PF lag

Q (-)

S

S

P (-)

P (+)

P (-)

P (+)

S

S

Q (+)

PF lag

+P

(+kW)

PF lead

Q (-)

 

Quadrant 3

Quadrant 4

 

 

 

-Q

 

 

 

 

 

(-kVAR)

 

 

 

PF lead / lag summary

 

 

 

 

 

 

 

 

Quadrant

 

Current phase shift

Load type

PF lead / lag

 

 

 

 

 

 

Quadrant 1

 

Current lags voltage

 

Inductive

PF lag

 

 

 

 

 

 

Quadrant 2

 

Current leads voltage

 

Capacitive

PF lead

 

 

 

 

 

 

Quadrant 3

 

Current lags voltage

 

Inductive

PF lag

 

 

 

 

 

 

Quadrant 4

 

Current leads voltage

 

Capacitive

PF lead

 

 

 

 

 

 

PF sign convention

The meter shows positive or negative power factor according to IEC standards.

PF sign in IEC

The meter correlates power factor sign (PF sign) with the direction of real power (P) flow.

For positive real power (+P), the PF sign is positive (+).

For negative real power (-P), the PF sign is negative (-).

+Q

(+kVAR)

Quadrant 2

Quadrant 1

Q (+)

PF sign -

-P (-kW)

PF sign -

Q (-)

S

S

P (-)

P (+)

P (-)

P (+)

S

S

Q (+)

PF sign +

+P

(+kW)

PF sign +

Q (-)

Quadrant 3

Quadrant 4

-Q (-kVAR)