iEM3100 / iEM3200 / iEM3300 series user manual

Front panel display and meter setup

 

 

 

 

 

 

 

 

 

 

 

Section

Parameter

Options

Description

 

 

 

 

 

 

 

Primary Addr.

0 - 255

Set the address for this device. The address must be unique for each device in a

 

 

communications loop.

 

 

 

 

 

 

 

2400

 

 

Communication (iEM3235)

 

4800

 

 

 

9600

Select the speed for data transmission. The baud rate must be the same for all devices

 

 

Baud Rate

 

 

300

in a communications loop.

 

 

 

 

 

 

600

 

 

 

 

1200

 

 

 

 

 

 

 

 

MAC Addr.

1 - 127

Set the address for this device. The address must be unique for each device in a

 

 

communications loop.

 

 

 

 

 

 

 

9600

 

 

 

 

19200

Select the speed for data transmission. The baud rate must be the same for all devices

 

Communication (iEM3265)

Baud Rate

38400

 

in a communications loop.

 

 

 

57600

 

 

 

 

 

 

 

76800

 

 

 

 

 

 

 

 

Device ID

0 - 4194303

Set the Device ID for this device. Make sure the Device ID is unique in your BACnet

 

 

network.

 

 

 

 

 

Com.Protection

Com.Protection

Enable

Protects selected settings and resets from configuration via communications.

 

Disable

 

 

 

 

 

 

 

 

 

 

Contrast

Contrast

1-9

Increase or decrease the value to increase or decrease the display contrast.

 

 

 

 

 

 

Password

Password

0-9999

Sets the password for accessing the meter configuration screens and resets.

 

 

 

 

 

 

Reset Config

Reset Config

Settings are reset to their defaults, except for Password. Meter restarts.

 

 

 

 

 

 

DOCA0005EN-04

49