Table 13ÐStorage Failure Errors
Error Display (Dial Position T4) must be turned on.
SF ERROR CODE | DESCRIPTION |
| SOLUTION | |
|
|
| ||
01 | Temperature Programming Error | Reprogram the scheduled temperatures. | ||
|
|
| ||
02 | Time Period Programming Error | Reprogram the scheduled time periods. | ||
03 | Zone 1 Temperature Calibration Out | 1. | Turn selection dial to position 2. | |
2. | Change temperature value. | |||
of Range | ||||
| 3. | Return selection dial to any run mode position. Valid temperature range = 30°Ð180°F. | ||
|
| |||
|
|
|
| |
04 | Zone 2 Temperature Calibration Out | 1. | Turn selection dial to position 3. | |
2. | Change temperature value. | |||
of Range | ||||
| 3. | Return selection dial to any run mode position. Valid temperature range = 30°Ð180°F. | ||
|
| |||
|
|
|
| |
05 | Zone 3 Temperature Calibration Out | 1. | Turn selection dial to position 4. | |
2. | Change temperature value. | |||
of Range | ||||
| 3. | Return selection dial to any run mode position. Valid temperature range = 30°Ð180°F. | ||
|
| |||
06 | Zone 4 Temperature Calibration Out | 1. | Turn selection dial to position 5. | |
2. | Change temperature value. | |||
of Range | ||||
| 3. | Return selection dial to any run mode position. Valid temperature range = 30°Ð180°F. | ||
|
| |||
|
|
|
| |
07 | Duct Temperature Calibration Out of | 1. | Turn selection dial to position 6. | |
2. | Change temperature value. | |||
Range | ||||
| 3. | Return selection dial to any run mode position. Valid temperature range = 30°Ð180°F. | ||
|
| |||
08 | Outside Temperature Calibration Out | 1. | Turn selection dial to position 7. | |
2. | Change temperature value. | |||
of Range | ||||
| 3. | Return selection dial to any run mode position. Valid temperature range = 30°Ð120°F. | ||
|
| |||
|
|
|
| |
09 | Dx Coil Temperature Calibration Out | 1. | Turn selection dial to position 8. | |
2. | Change temperature value. | |||
of Range | ||||
| 3. | Return selection dial to any run mode position. Valid temperature range = 30°Ð180°F. | ||
|
| |||
|
|
|
| |
|
| 1. | Turn selection dial to position S. | |
10 | LAT Error | 2. | Select variable number 6. | |
3. | Enter a new value. | |||
|
| |||
|
| 4. | Return selection dial to any run mode position. | |
|
|
|
| |
|
| 1. | Turn selection dial to position S. | |
11 | Device Address Error | 2. | Verify correct address of the 4 zone controller is as shown in the Programming and Operation | |
| Section. | |||
|
|
| ||
|
| 3. | Verify smart sensor address(es) are as shown in the Programming and Operation Section. | |
|
|
|
| |
12 |
| 1. | Turn selection dial to position T2, T11, T12, T18, T20, T22, and T24. | |
Configuration Error | 2. Check and correct the configuration. | |||
|
| 3. | Return selection dial to any run mode position. | |
|
|
|
| |
13 |
| 1. | Turn selection dial to position T4, T5, T6, T13, and T17. | |
Configuration Error | 2. Check and correct the configuration. | |||
|
| 3. | Return selection dial to any run mode position. | |
14 |
| 1. | Turn selection dial to position T7, T8, T9, T10, T19, T21, T23, and T25. | |
Configuration Error | 2. Check and correct the configuration. | |||
|
| 3. | Return selection dial to any run mode position. | |
|
|
|
| |
15 |
| 1. | Turn selection dial to position T26 and T27. | |
Configuration Error | 2. Check and correct the configuration. | |||
|
| 3. | Return selection dial to any run mode position. | |
16 | Configuration Error | Push HOLD button on/off. | ||
|
|
|
| |
|
| 1. | Turn the error display T4 off. | |
17 | Current Setpoints | 2. | Change any setpoint. | |
3. | Turn the error display T4 on. | |||
|
| |||
|
| 4. | Return selection dial to any run mode position. | |
|
|
|
| |
|
| 1. | Turn the error display T4 off. | |
18 |
| 2. | Turn the selection dial to Vacation. | |
Vacation Setpoints | 3. Change any setpoint. | |||
|
| 4. | Turn the error display T4 on. | |
|
| 5. | Return selection dial to any run mode position. | |
|
|
|
| |
|
| 1. | Turn selection dial to position S. | |
19 | Maximum/Minimum Temperature Set- | 2. Change the maximum cooling setpoint (S2). Must be outside 14° range. | ||
points | 3. Change the minimum heating setpoint (S3). Must be outside 14° range. | |||
| ||||
|
| 4. | Return selection dial to any run mode position. | |
|
|
|
| |
|
| 1. | Turn the selection dial to position S. | |
20 | Maximum/Minimum Damper Ventila- | 2. Change the maximum damper position (S4). Default = 15. | ||
tion | 3. Change the vent damper position (S5). Default = 0. | |||
| ||||
|
| 4. | Return selection dial to any run mode position. | |
21 |
| 1. | Turn the selection dial to position 1. | |
Bypass Damper Total | 2. | |||
|
|
| tion. | |
|
|
|
| |
22 |
| 1. | Turn selection dial to position T1. | |
Baud Rate | 2. Toggle the baud rate twice (T3). | |||
|
| 3. | Return selection dial to any run mode position. | |
23 |
| 1. | Turn selection dial to position S7. | |
Dual Fuel Trip Temperature Error | 2. Change the value. | |||
|
| 3. | Return selection dial to any run mode position. | |
|
| 1. | Turn selection dial to position 9. | |
24 | Base Temperatures Error | 2. | Set base temperatures. Do not overlap with 14° maximum cooling/minimum heating set point | |
| range. | |||
|
|
| ||
|
| 3. | Return selection dial to any run mode position. | |
|
|
|
|
20