Carrier ZONEKIT4ZCAR instruction manual ÐOperating Problems

Models: ZONEKIT4ZCAR

1 32
Download 32 pages 21.57 Kb
Page 19
Image 19
Table 12ÐOperating Problems

 

 

Table 12ÐOperating Problems

 

 

 

SYMPTOM

 

POSSIBLE CAUSE

 

Thermostat is not receiving power.

 

1.

Verify that comfort zone center is receiving 24 vac. (50 va minimum required with 4 motorized

No Display

 

dampers, 5 va for each additional motorized damper.)

2.

Check that the thermostat is receiving a steady 10 VDC across the red and white wires at the

 

 

 

system controller terminal block on the comfort zone, I/O board, and on the Red/White terminals

 

 

on the base plate of the 4 zone controller.

 

Low voltage.

 

1.

Verify that the comfort zone center is receiving 24 vac. (50 va minimum required with motorized

 

 

dampers, 5 va for each additional motorized damper.)

 

2.

Check that the thermostat is receiving a steady 10 VDC across the red and white wires at the

Blinking Temperature Display

 

system controller terminal block on the comfort zone, I/O board, and on the red/white terminals

 

on the base of the 4 zone controller.

 

3.

Check that the yellow or blue wires are connected properly and not broken at the system control-

 

 

ler terminal block on the comfort zone I/O board and on the yellow/blue terminal on the base of

 

 

the 4 zone controller.

 

4.

Verify that the terminals are properly installed on the base plate of the controller.

 

5.

Wiring connector block for smart sensor could be defective.

Blinking HEAT or COOL Annunciator

1.

Check to see if high/low temperature trip limits have been exceeded.

2.

Temperature sensor is improperly wired or defective.

 

Cooling or Heating is Requested But

1. Must have at least 1 zone with a demand greater than 1.5° F from setpoints.

The HEAT or COOL Annunciator is

2. Check system switches. They must be set to AUTO or ON to operate.

not displayed

3.

Have you waited for timeguard (5 minutes) to expire?

COOL or HEAT Annunciator is Lit

1.

Check that the LEDs on the CHR06 relay pack are indicating the correct relay is closed. If not,

 

check for a bad relay.

But Cool or Heat is Not On

2.

Measure voltage across common (red) and any de-energized relay. Voltage should be 24 vac.

 

3.

Apply 24 vac directly across relay.

1.Verify that there are no obstructions binding the damper blade or shaft.

2.Check for 24 vac across common and either the open or close terminals.

Damper Will Not Open or Close 3. Check stop switch. If defective, replace actuator.

4.Verify that motor is operating correctly.

5.Check damper fuse.

System is Too Noisy

1.

Make sure bypass damper is working properly.

2.

Verify that duct work is properly sized.

 

Unstable Temperature Readings

1.

Check for drafts.

2.

Use shielded cable.

 

 

1.

Make sure that the sensor wire is not run in parallel with any wires carrying AC voltage.

 

2.

Disconnect all other sensors from the comfort zone I/O board and check to see if the sensor

 

 

reading is still fluctuating.

 

3.

Disconnect all other sensors from the comfort zone panel and check to see if the problem still

 

 

exists.

 

4.

Disconnect the 4 zone controller and re-wire it directly to the I/O board with a separate

 

 

5-conductor cable.

 

5.

If all sensors are still fluctuating, replace the 4 zone controller.

Room Sensors Fluctuating

6.

If only 1 sensor is fluctuating, disconnect that sensor from the I/O board and re-wire it directly to

 

the I/O board using a separate 2-conductor cable.

 

7.

If the sensor still has the problem, replace the I/O board.

 

8.

Verify if shielded or non-shielded cable is being used.

 

9.

If shielded, follow through the remaining steps. If non-shielded, go to No. 6.

 

10. Verify that the shield is connected to the comfort zone panel and that the panel is properly

 

 

grounded to the chassis.

 

11. Remove the shield wire and check to see if the problem still exists.

 

12. Verify that the shield wire has been clipped off at the sensor end and is not touching any other

 

 

wires or any exposed metal.

 

13. Ensure that there is a solid electrical ground on the electric power box.

19

Page 19
Image 19
Carrier ZONEKIT4ZCAR instruction manual ÐOperating Problems