![Fig. 3ÐTypical Communications Network](/images/new-backgrounds/33652/336525x1.webp)
NOTE 2
NOTE 2
|
| PORT #1 | |
|
| PORT #2 | |
|
| ||
|
|
| |
|
|
|
|
|
|
|
|
PORT #1
PORT #2
Comfort | Comfort |
Zone | Zone |
I/O | I/O |
ISOSAT BUS | NOTE 1 |
|
Comfort
Zone
I/O
NOTE 2
Comfort | Comfort |
Zone | Zone |
I/O | I/O |
ISOSAT BUS | NOTE 1 |
|
Comfort
Zone
I/O
NOTE 2
|
|
|
| SHIELD DRAIN WIRE (TYP) |
|
|
| PORT #1 | |
|
|
| PORT #2 | |
|
|
| ||
|
|
| ||
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
SHIELD DRAIN WIRE (TYP)
PORT #1 |
|
PORT #2 | |
|
|
|
|
|
|
| DEVICE BUS (TYP) | ||
|
|
|
|
|
| |||
|
|
|
|
| SHIELD DRAIN WIRE (TYP) | |||
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| PORT #1 |
|
| |
|
|
|
|
| PORT #2 |
|
| |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| NOTES: |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| 1. Use butt splices, or solder, |
|
|
|
|
|
|
|
| for shield connections. Then |
|
|
|
|
|
|
|
| tape up shield. |
|
|
|
|
| PORT #1 |
|
| 2. Do not connect the shield |
|
|
|
|
|
|
|
| |
|
|
|
|
| PORT #2 |
| drain wire at the end of | |
|
|
|
|
|
|
| Communication Bus. Cut | |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| and tape up to avoid shorting. |
|
|
|
|
|
|
|
|
DEVICE BUS (TYP)
SHIELD DRAIN WIRE (TYP)
|
|
|
|
| PORT #1 | |
|
|
|
|
| ||
|
|
|
|
| PORT #2 | |
|
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| PORT #1 | |
|
|
| ||
|
|
| PORT #2 | |
|
|
| ||
|
|
| ||
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
NOTES:
1.Use butt splices, or solder, for shield connections. Then tape up shield.
2.Do not connect the shield drain wire at the end of Communication Bus. Cut and tape up to avoid shorting.
BUILDING GROUND |
|
| ||
|
|
| A93249 | |
Fig. 3ÐTypical Communications Network | ||||
Table 1ÐWiring Requirements |
| |||
|
|
|
| |
FROM | NO. |
| MAX. | |
COMFORT ZONE | GAGE | LENGTH | ||
OF WIRES | ||||
CENTER TO |
| (FT) | ||
|
| |||
Four Zone Controller | 3³ | 18/22 | 200/100 | |
|
|
| ||
5³ | 18/22 | 200/100 | ||
| ||||
|
|
|
| |
Remote Room Sen- | 2³ | 18/22 | 200/100 | |
sors | ||||
|
|
| ||
Remote Duct Sensors | 2³ | 18/22 | 200/100 |
TO PERSONAL COMPUTER OR MODEM
PORT #1
PORT #2
BUILDING GROUND
Fig. 4ÐCommunication Network With
An
A93250
Dx Coil Sensor | 2³ | 18/22 | 200/100 | |
Home Access | 3³ | 18/22 | 1000/100 | |
Module | ||||
|
|
| ||
ISOSAT* | 3³ | 18/22 | 1000/100 | |
Transformer² | 2 | 18 | 75 |
*When using ISOSATS in interfacing multiple buses together, the length of wiring between ISOSATS cannot exceed 4000 ft with 18 gage.
² 24 vac,
³ Shielded cable recommended to reduce noise interference.
Step 3ÐInstall Comfort Zone Center
NOTE: The Comfort Zone System is approved for indoor use only and should never be installed with any of its components exposed to the elements. The enclosure must be installed with center cover to help prevent damage from other sources. Do not mount Comfort Zone Center where it will be accessible to children. Do not locate center in areas of the home that are noise sensitive since relays are energized and
Install Comfort Zone Center in either a vertical or horizontal position. Locate in an area that is easily accessible in case servicing should be required.
NOTE: Four vent plugs and 2 bushings have been supplied. Snap bushings in the
To prevent possible damage to Comfort Zone Center, do not mount on plenum, duct work, or flush against furnace.
1.Separate Comfort Zone Center cover. (See Fig. 5)
2.Mount back plate of center cover to wall using screws and wall anchors provided.
3.Level back plate and tighten screws.
Step 4ÐInstall Zone Dampers
IMPORTANT: If conditions exist for possible condensing, motor must be positioned for adequate draining. (See Fig. 6.)
NOTE: If a
Zone dampers may be installed in any direction.
Install dampers so that actuator is visible for inspection and accessible in the event it would ever need to be serviced. The black mark on the end of damper shaft represents the position of damper blade.
NOTE: Insulate damper using
3