Schneider Electric iEM3300 Instantaneous RMS measurements, Meter information, DOCA0005EN-04

Models: iEM3100 iEM3200 iEM3300

1 112
Download 112 pages 230 b
Page 93
Image 93
Instantaneous (RMS) measurements

iEM3100 / iEM3200 / iEM3300 series user manualCommunications via BACnet

Instantaneous (RMS) measurements

Object ID

Units

Default COV

Object name / description

 

 

 

 

7

A

50

AI07 - Current Phase 1

 

 

 

 

8

A

50

AI08 - Current Phase 2

 

 

 

 

9

A

50

AI09 - Current Phase 3

 

 

 

 

10

A

50

AI10 - Current Average

 

 

 

 

11

V

10

AI11 - Voltage L1-L2

 

 

 

 

12

V

10

AI12 - Voltage L2-L3

 

 

 

 

13

V

10

AI13 - Voltage L3-L1

 

 

 

 

14

V

10

AI14 - Voltage Average L-L

 

 

 

 

15

V

10

AI15 - Voltage L1-N

 

 

 

 

16

V

10

AI16 - Voltage L2-N

 

 

 

 

17

V

10

AI17 - Voltage L3-N

 

 

 

 

18

V

10

AI18 - Voltage Average L-N

 

 

 

 

19

kW

10

AI19 - Active Power Phase 1

 

 

 

 

20

kW

10

AI20 - Active Power Phase 2

 

 

 

 

21

kW

10

AI21 - Active Power Phase 3

 

 

 

 

22

kW

10

AI22 - Active Power Total

 

 

 

 

23

kVAR

10

AI23 - Reactive Power Total

 

 

 

 

24

kVA

10

AI24 - Apparent Power Total

 

 

 

 

25

0.2

AI25 - Power Factor Total

 

 

 

 

26

Hz

10

AI26 - Frequency

 

 

 

 

Meter information

The following AI objects display information about the meter and its configuration.

NOTE: You can access the meter’s configuration information over BACnet communications.

However, you must use the front panel to configure the meter’s settings.

Object ID

Units

Default COV

Object name / description

 

 

 

 

44

Seconds

10

AI44 - Meter operation time

The time in seconds since the meter was last powered up

 

 

 

 

 

 

 

45

1

AI45 - Number of phases

1, 3

 

 

 

46

1

AI46 - Number of wires

2, 3, 4

 

 

 

 

 

 

 

 

 

 

AI47 - Power system type

 

 

 

0 = 1PH2W L-N

 

 

 

1 = 1PH2W L-L

47

1

2 = 1PH3W L-L with N

 

 

 

3 = 3PH3W

 

 

 

11 = 3PH4W

 

 

 

13 = 1PH4 wire multi L-N

 

 

 

 

48

Hz

1

AI48 - Nominal frequency

50, 60

 

 

 

 

 

 

 

 

 

 

AI49 - Number of VTs

49

1

0 - 10

 

 

 

NOTE: only applies to the iEM3265

50

V

1

AI50 - VT Primary

NOTE: only applies to the iEM3265

 

 

 

51

V

1

AI51 - VT Secondary

NOTE: only applies to the iEM3265

 

 

 

 

 

 

AI52 - Number of CTs

52

1

1, 2, 3

 

 

 

NOTE: only applies to the iEM3265

53

A

1

AI53 - CT Primary

NOTE: only applies to the iEM3265

 

 

 

DOCA0005EN-04

93

Page 93
Image 93
Schneider Electric iEM3300, iEM3200, iEM3100 user manual Instantaneous RMS measurements, Meter information, DOCA0005EN-04