Schneider Electric iEM3200 Configuration menus for iEM3250, Front panel display and meter setup

Models: iEM3100 iEM3200 iEM3300

1 112
Download 112 pages 230 b
Page 46
Image 46
Configuration menus for iEM3250

Front panel display and meter setup

 

 

 

 

 

 

 

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Section

Parameter

 

 

 

 

Options

 

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Select the tariff control mode:

 

 

 

 

 

 

 

 

 

 

 

 

• Disable: the Multi Tariff function is disabled.

 

 

 

 

 

 

 

 

 

 

 

 

• by Digital Input: the digital input is associated with the multi-tariff

 

Multi Tariffs (iEM3215)

Control Mode

 

 

 

 

Disable

 

 

function. A signal to the digital input changes the active tariff.

 

 

 

 

 

by Internal Clock

 

 

• by Internal Clock: the device clock controls the active tariff. If you set the

 

 

 

 

 

 

 

 

 

 

 

Control Mode to by Internal Clock, you must also configure the schedule.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set the time when each tariff period starts, using the 24 hour clock format

 

 

 

 

 

 

 

 

 

 

 

 

(00:00 to 23:59). The start time of the next tariff is the end time of the

 

 

 

 

 

 

 

 

 

 

 

 

current tariff. For example, T2 start equals the end of T1.

 

Contrast

Contrast

 

 

1-9

 

 

Increase or decrease the value to increase or decrease the display contrast.

 

Password

Password

 

 

0-9999

 

 

Sets the password for accessing the meter configuration screens and resets.

 

(iEM3210 / iEM3215)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reset Config

Reset Config

 

 

 

 

 

 

Settings are reset to their defaults, except for Password. Meter restarts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuration menus for iEM3250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wiring

 

 

 

 

Type

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency

 

 

 

 

 

 

Frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Date

 

 

 

 

Date

 

 

 

 

 

Time

 

 

 

 

 

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication

 

 

 

 

 

Slave Address

 

 

 

 

 

 

 

 

 

 

 

 

Baud Rate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parity

 

 

 

 

 

Contrast

 

 

 

 

 

 

Contrast

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reset Config

 

 

 

 

 

 

Reset Config

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Section

Parameter

 

 

 

 

 

 

Options

 

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3PH4W

 

 

 

 

 

 

 

 

1PH2W L-N

 

 

 

 

Wiring

Type

 

 

1PH2W L-L

 

Select the power system type the meter is wired to.

 

 

1PH3W L-L-N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3PH3W

 

 

 

 

 

 

 

 

1PH4W Multi L-N

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency

Frequency

 

 

50

 

Select the frequency of the electrical power system, in Hz.

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Date

Date

 

 

DD-MMM-YYYY

 

Set the current date using the specified format.

 

 

 

 

 

 

 

 

Time

Time

 

 

hh:mm

 

Set the time using the 24-hour format.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slave Address

 

 

1 - 247

 

Set the address for this device. The address must be unique for each device in

 

 

 

 

a communications loop.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19200

 

Select the speed for data transmission. The baud rate must be the same for all

 

 

Baud Rate

 

 

38400

 

 

Communication

 

 

devices in a communications loop.

 

 

 

 

9600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Even

 

Select None if the parity bit is not used. The parity setting must be the same for

 

 

Parity

 

Odd

 

all devices in a communications loop.

 

 

 

 

 

None

 

NOTE: Number of stop bits = 1.

 

 

 

 

 

 

 

 

Contrast

Contrast

 

 

1-9

 

Increase or decrease the value to increase or decrease the display contrast.

 

 

 

 

 

 

 

 

Reset Config

Reset Config

 

 

 

Settings are reset to their defaults, except for Password. Meter restarts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

46