Schneider Electric iEM3300 Power system configuration information, Communications via M-Bus

Models: iEM3100 iEM3200 iEM3300

1 112
Download 112 pages 230 b
Page 81
Image 81
Power system configuration information

iEM3100 / iEM3200 / iEM3300 series user manual

Communications via M-Bus

 

 

Power system configuration information

NOTE: E denotes the extension bit; the hex value assumes E = 0.

Data format

Manufacturer-specific VIFE

Description

 

 

bin

hex

 

 

 

 

 

 

 

 

 

Power system configuration:

 

 

 

0 = 1PH2W L-N

 

 

 

1 = 1PH2W L-L

03

E010 0011

23

2 = 1PH3W L-L with N

 

 

 

3 = 3PH3W

 

 

 

11 = 3PH4W

 

 

 

13 = 1PH4 wire multi L with N

 

 

 

 

03

E010 0010

22

Number of wires

2, 3, 4

 

 

 

 

 

 

 

03

E010 0001

21

Number of phases

1, 3

 

 

 

 

 

 

Number of CTs

03

E010 1000

29

1, 2, 3

 

 

 

NOTE: only applies to the iEM3235

 

 

 

Number of VTs

03

E010 0101

25

0-10

 

 

 

NOTE: only applies to the iEM3235

05

E010 0110

26

VT Primary

NOTE: only applies to the iEM3235

 

 

 

03

E010 0111

27

VT Secondary

NOTE: only applies to the iEM3235

 

 

 

03

E010 1001

29

CT Primary

NOTE: only applies to the iEM3235

 

 

 

03

E010 1010

2A

CT Secondary

NOTE: only applies to the iEM3235

 

 

 

 

 

 

VT connection type

03

E010 1011

2B

0 = Direct connection, no VTs

1 = 3PH3W (2VTs)

 

 

 

 

 

 

2 = 3PH4W (3VTs)

 

 

 

 

03

E010 0100

24

Nominal frequency

50, 60

 

 

 

Digital input and output status information

NOTE: E denotes the extension bit; the hex value assumes E = 0.

Data format

Primary VIFE

Manufacturer-specific VIFE

 

Description

 

 

 

 

 

bin

hex

bin

hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital input control mode:

 

 

 

 

 

0

= Normal (Input Status)

03

E001 1011

1B

2 = Multi Tariff control

 

 

 

 

 

3

= Input metering

 

 

 

 

 

5

= All partial energy logs reset

05

E010 1111

2F

Pulse constant (pulses/unit)

 

 

 

 

 

Digital input status:

 

 

 

 

 

0

= relay open

02

E011 0010

32

1

= relay closed

 

 

 

 

 

NOTE: This information only applies if the digital input control mode is set

 

 

 

 

 

to Input Status.

 

 

 

 

 

Digital input association with partial energy data reset

03

E011 0000

30

0

= Digital input is not associated with the partial energy reset

 

 

 

 

 

1

= Digital input is associated with the partial energy reset

 

 

 

 

 

 

 

 

 

 

 

Energy pulse duration in milliseconds

03

E010 1100

2C

NOTE: This information only applies if the digital output mode is set to

 

 

 

 

 

energy pulsing.

DOCA0005EN-04

81

Page 81
Image 81
Schneider Electric iEM3300, iEM3200 Power system configuration information, Digital input and output status information