Communications via M-BusiEM3100 / iEM3200 / iEM3300 series user manual

Communications setup

SND_UD code

Data format

Primary VIF

Range/options

Description

 

 

 

 

 

00

01

7A

0-250

Primary address

 

 

 

 

 

To change the baud rate via communications, send a telegram to the meter with the appropriate value in the CI-field:

Baud rate

Hex value for CI-field

 

 

300

B8

 

 

600

B9

 

 

1200

BA

 

 

2400

BB

 

 

4800

BC

 

 

9600

BD

 

 

Digital input setup

NOTE: E denotes the extension bit; the hex value assumes E = 0.

SND_UD

Data format

Manufacturer-specific VIFE

 

Range/options

 

Description

 

 

 

 

code

 

bin

hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital input control mode

00

02

E001 1011

1B

0, 3, 5

 

0

= Normal (Input Status)

 

3

= Input metering

 

 

 

 

 

 

 

 

 

 

 

 

5

= Partial energy reset

 

 

 

 

 

 

 

00

05

E010 1111

2F

1-10000

 

Pulse constant (pulses/unit; applicable when the digital

 

input is used for input metering)

 

 

 

 

 

 

Digital output setup

NOTE: E denotes the extension bit; the hex value assumes E = 0.

SND_UD

Data format

Manufacturer-specific VIFE

Range/options

Description

 

 

 

code

 

bin

 

hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital output control mode

00

02

E001 1010

1A

 

2, 3, 0xFFFF

2 = Alarm

 

3 = Energy (energy pulsing)

 

 

 

 

 

 

 

 

 

 

 

 

0xFFFF = Disable

 

 

 

 

 

 

 

 

 

 

 

 

iEM3135 / iEM3335: 1, 10, 20, 100,

Pulse constant

00

05

E010 1110

2E

 

200, 1000

NOTE: This information only applies if the digital output

 

 

 

 

 

iEM3235: 0.01, 0.1, 1, 10, 100, 500

control mode is set to for Pulse.

 

 

 

 

 

 

Pulse width in ms

00

02

E010 1100

2C

 

50, 100, 200, 300

NOTE: This information only applies if the digital output

 

 

 

 

 

 

control mode is set to for Pulse.

Overload alarm setup and acknowledgment

Use the information in the table below to configure the overload alarm.

NOTE: E denotes the extension bit; the hex value assumes E = 0.

SND_UD

Data format

Manufacturer-specific VIFE

Range/options

Description

 

 

code

 

bin

hex

 

 

 

 

 

 

 

 

 

 

 

 

00

05

E011 0101

35

0 - 9999999

The pickup setpoint in kW for the

overload alarm

 

 

 

 

 

 

 

 

 

 

Overload alarm setup:

00

02

E011 0100

34

0,1

0 = Disable

 

 

 

 

 

1 = Enable

 

 

 

 

 

 

84

DOCA0005EN-04

Page 84
Image 84
Schneider Electric iEM3300 Digital input setup, Digital output setup, Overload alarm setup and acknowledgment, Baud rate