Front panel display and meter setup

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

Setting the clock initially

The following diagram illustrates how to set the clock when you initially power up the device or after a power failure. To set the clock during normal operation, see the section on device configuration.

Date & Time

Set?

OK

Password

 

 

 

 

 

Date

 

 

 

 

Time

 

 

 

 

 

Date & Time

 

OK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0010

 

 

 

 

 

 

01-Jan-2000

 

 

 

 

 

00:00

 

 

 

 

Save Settings?

 

 

 

 

 

OK

 

 

DD-MM-YYYY

 

 

OK

 

 

hh:mm

 

 

OK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Password entry is only required for meters that support a password.

OK

Total Active E

1234.5

kWh

Related topics

See “Device configuration” on page 38 for information on setting the clock during normal device operation.

Device configuration

The default factory settings are listed in the following table:

Menu

Factory settings

 

 

 

iEM31••: 3PH4W

Wiring

iEM32••: 3PH4W; 3 CTs on I1, I2, and I3; Direct-No VT

 

iEM33••: 3PH4W

CT Ratio

CT Secondary = 5 A; CT Primary = 5 A

CT & VT Ratio

CT Secondary = 5 A; CT Primary = 5 A

VT Secondary = 100 V; VT Primary = 100 V

 

 

 

Frequency

50 Hz

 

 

Date

1-Jan-2000

 

 

Time

00:00:00

 

 

Multi Tariffs

Disable

 

 

Overload Alarm

Disable

 

 

Digital Output

Disable

 

 

Digital Input

Input Status

 

 

Pulse Output

100 imp / kWh

 

 

Communication

Varies depending on protocol

 

 

Com.Protection

Enable

 

 

Contrast

5

 

 

Password

0010

 

 

Entering configuration mode

1.Press and hold OK and ESC at the same time for about 2 seconds.

2.Enter the meter password, if prompted. The Access Counter screen displays, indicating the number of times the configuration mode has been accessed.

Config

> 2s

The front panel display in configuration mode

The diagram below illustrates the various elements of the display in configuration mode:

..\In. Pulse Const.

A

Parameter

B

Setting

 

00500

C

Configuration mode icon

D Indicates that the setting impacts the Multi Tariff feature

 

 

Overriding!

 

 

38

DOCA0005EN-04

Page 38