Communications via BACnet

 

 

 

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

 

 

 

 

 

 

 

 

Device object property

R/W

Stored

Possible values

Description

 

 

 

 

 

Local_Time

R

configurable

Time

NOTE: You must use the front panel to set the meter’s time.

 

 

 

 

APDU_Timeout

R/W

1000 - 30000

The amount of time (in milliseconds) before the meter tries to resend a confirmed

message that has not been answered.

 

 

 

 

Number_Of_APDU_Retries

R/W

1 - 10

The number of times the meter tries to resend an unanswered confirmed

request.

 

 

 

 

Max_Master

R/W

1 - 127

The highest master address the meter will try to discover when the next node is

unknown.

 

 

 

 

Max_Info_Frames

R/W

1 - 14

Maximum number of messages the meter can send before it must pass the

token.

 

 

 

 

Device_Address_Binding

R

Device address binding table is always blank because the meter does not initiate

the who-Is service.

 

 

 

 

Database_Revision

R

varies

A number that increments when the object database on the meter changes (for

example, when an object is created or deleted or the ID of an object changes).

 

 

 

 

Active_COV_Subscriptions

R

varies

List of COV subscriptions currently active on the meter.

 

 

 

 

 

Profile_Name

R

varies

Device identifier, used on these meters to record the meter manufacturer, the

meter family and the specific meter model (for example, 10_iEM3000_iEM3265).

 

 

 

 

ID 800

R

varies

Date and time of last energy reset

ID 801

R

varies

Date and time of last input metering accumulation reset

ID 802

R

varies

Date and time of the last alarm (DD/MM/YYYY hh:mm:ss)

Related topics

See “Device configuration” on page 38 for information on configuring the meter using the front panel.

Analog Input objects

The following tables list the Analog Input (AI) objects along with the units and default COV value for each AI object (if applicable).

NOTE: The Value Type for all AI objects is Real.

Energy and energy by tariff measurements

The energy and energy by tariff measurements listed below are preserved through power failures.

Object ID

Units

Default COV

Object name / description

 

 

 

 

27

Wh

100

AI27 - Total active energy import

28

Wh

100

AI28 - Total active energy export

29

Wh

100

AI29 - Total reactive energy import

30

Wh

100

AI30 - Total reactive energy export

31

Wh

100

AI31 - Partial active energy import

32

Wh

100

AI32 - Partial reactive energy import

33

Wh

100

AI33 - Active energy import phase 1

34

Wh

100

AI34 - Active energy import phase 2

35

Wh

100

AI35 - Active energy import phase 3

36

10

AI36 - Accumulation

Input metering accumulation

 

 

 

 

 

 

 

 

 

 

AI37 - Tariff Energy Active Rate

 

 

 

Denotes the active tariff:

 

 

 

0

= Multi Tariff feature is disabled

37

1

1

= rate A (tariff 1) active

 

 

 

2

= rate B (tariff 2) active

 

 

 

3

= rate C (tariff 3) active

 

 

 

4

= rate D (tariff 4) active

 

 

 

 

38

Wh

100

AI38 - Rate A (Tariff 1) active energy import

 

 

 

 

39

Wh

100

AI39 - Rate B (Tariff 2) active energy import

 

 

 

 

40

Wh

100

AI40 - Rate C (Tariff 3) active energy import

 

 

 

 

41

Wh

100

AI41 - Rate D (Tariff 4) active energy import

 

 

 

 

 

92

DOCA0005EN-04

Page 92
Image 92
Schneider Electric iEM3100, iEM3300, iEM3200 user manual Analog Input objects, Energy and energy by tariff measurements