Schneider Electric iEM3200 Command Interface, Communications via Modbus RS-485, DOCA0005EN-04

Models: iEM3100 iEM3200 iEM3300

1 112
Download 112 pages 230 b
Page 58
Image 58
Command Interface

Communications via Modbus RS-485

 

 

 

 

 

 

 

 

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Register

Action

Size

 

Type

 

Units

 

 

Description

 

Address

(R/W/WC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2031

R/WC

1

 

UInt16

 

A

 

CT Secondary

 

 

 

 

Not applicable for iEM3150 / iEM3155 / iEM3350 / iEM3355

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VT Connection Type

 

 

 

 

 

 

 

 

 

0 = Direct Connect

 

2036

R/WC

1

 

UInt16

 

 

1 = 3PH3W (2 VTs)

 

 

 

 

 

 

 

 

 

2 = 3PH4W (3 VTs)

 

 

 

 

 

 

 

 

 

Not applicable for iEM3150 / iEM3155 / iEM3350 / iEM3355

 

Energy Pulse Output Setup (iEM3155 / iEM3255 / iEM3355)

 

 

 

 

 

 

 

 

 

 

 

 

Register

Action

Size

 

Type

 

Units

 

 

Description

 

Address

(R/W/WC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2129

R/WC

1

UInt16

Millisecond

 

Energy Pulse Duration

 

 

 

 

 

 

 

 

 

 

Digital Output Association

 

2131

R/WC

1

UInt16

 

 

0 = Disable

 

 

 

 

 

 

 

 

 

 

1 = DO1 enable for active energy pulse output

 

 

 

 

 

 

 

 

 

 

2132

R/WC

2

Float32

pulse/kWh

 

Pulse Weight

 

 

 

 

 

 

 

 

 

 

 

 

Command Interface

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Register

Action

Size

 

Type

Units

 

 

Description

 

Address

(R/W/WC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5250

R/W

1

UInt16

Requested Command

 

 

 

 

 

 

 

 

5252

R/W

1

UInt16

Command Parameter 001

 

 

 

 

 

 

 

 

5374

R/W

1

UInt16

Command Parameter 123

 

 

 

 

 

 

 

 

5375

R

1

UInt16

Command Status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Command Result codes:

 

 

 

 

 

 

 

 

0 = Valid Operation

 

5376

R

1

UInt16

3000 = Invalid Command

 

3001 = Invalid Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3002 = Invalid Number of Parameters

 

 

 

 

 

 

 

 

3007 = Operation Not Performed

 

 

 

 

 

 

 

 

5377

R/W

1

UInt16

Command Data 001

 

 

 

 

 

 

 

 

5499

R

1

UInt16

Command Data 123

 

 

 

 

 

 

 

 

 

 

 

 

Communication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Register

Action

Size

 

Type

Units

 

 

Description

 

Address

(R/W/WC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6500

R

1

UInt16

Protocol

 

0 = Modbus

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6501

R/WC

1

UInt16

Address

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Baud Rate:

 

6502

R/WC

1

UInt16

0 = 9600

 

1 = 19 200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 = 38 400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parity:

 

 

 

 

 

 

 

 

0 = Even

 

6503

R/WC

1

UInt16

1 = Odd

 

 

 

 

 

 

 

 

2 = None

 

 

 

 

 

 

 

 

NOTE: number of stop bits = 1

 

Input Metering Setup (iEM3155 / iEM3255 / iEM3355)

 

 

 

 

 

 

 

 

 

 

 

 

Register

Action

Size

 

Type

Units

 

 

Description

 

Address

(R/W/WC)

 

 

 

 

 

 

 

 

 

 

 

7032

R/WC

20

UTF8

Label

58

DOCA0005EN-04

Page 58
Image 58
Schneider Electric iEM3200, iEM3300 Command Interface, Communication, Input Metering Setup iEM3155 / iEM3255 / iEM3355