Schneider Electric iEM3100 Communications via BACnet, BACnet communications overview, Key terms

Models: iEM3100 iEM3200 iEM3300

1 112
Download 112 pages 230 b
Page 89
Image 89
Chapter 8 Communications via BACnet

iEM3100 / iEM3200 / iEM3300 series user manual

Communications via BACnet

 

 

Chapter 8 Communications via BACnet

What is in this chapter?

This chapter contains the following sections:

BACnet communications overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 BACnet protocol support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 BACnet communications implementation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 BACnet object and property information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

BACnet communications overview

Communications via BACnet MS/TP protocol is available on the iEM3165, iEM3265 and iEM3365.

The information in this section is intended for users with an advanced understanding of BACnet protocol, their communications network and their power system.

Key terms

Term

Definition

 

 

APDU

Application protocol data unit, that data portion of a BACnet message.

Confirmed message

A message for which the device expects an answer.

COV

Change of value, sets the amount by which a value has to change in order for the meter to send a

subscription notification.

 

 

A BACnet device is a unit that is designed to understand and use BACnet protocol (for example, a

Device

BACnet-enabled meter or software program). It contains information about the device and device

 

data in objects and object properties. Your meter is a BACnet device.

MS/TP

Master-slave/token-passing over RS-485.

Object

Represents the device and device data. Each object has a type (for example, analog input or binary

input) and has a number of properties.

 

Present value

The current value of an object.

 

 

Property

The smallest piece of information in BACnet communications, it consists of a name, data type and

value.

 

Service

Messages from one BACnet device to another.

 

 

 

Creates a relationship between the server and the meter, so that when the present value property

Subscription

of an object changes by more than the configured COV threshold (COV_Increment), a notification is

 

sent.

Subscription notification

The message the meter sends to indicate a COV event has occurred.

 

 

Unconfirmed message

A message for which the device does not expect an answer.

 

 

Related topics

See www.bacnet.org for more information on the BACnet protocol.

BACnet protocol support

Go to www.schneider-electric.com and search for your meter model to access the PICS (Protocol Implementation Conformance Statement) for your meter.

The meter supports the BACnet protocol as follows:

BACnet component

Description

 

 

Protocol version

1

 

 

Protocol revision

6

 

 

Standardized device profile (Annex L)

BACnet Application Specific Controller (B-ASC)

 

 

DOCA0005EN-04

89

Page 89
Image 89