iEM3100 / iEM3200 / iEM3300 series user manualCommunications via M-Bus

Variable data structure telegram information

Fixed data header

Byte 1-4

Byte 5-6

Byte 7

Byte 8

Byte 9

Byte 10

Byte 11-12

Identification No.

Manufacturer

Version

Medium

Access No.

Status

Signature

 

 

 

 

 

 

 

Serial number of the meter in an

 

Firmware version of the

 

 

 

 

8-digit, BCD coded format

4CA3 hex =

 

Counter of successful

Indicates M-Bus

 

communications board

02 hex (electricity)

Not used

The serial number can also be

Schneider Electric

access attempts

application errors

found on the meter front panel.

 

10 = version 1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data record header information

Data formats used by the meter (DIF bits 3-0)

NOTE: x in the hex value is determined by bits 7-4 of the DIF.

Format

bin

hex

 

 

 

No data

0000

x0

 

 

 

8-bit integer

0001

x1

 

 

 

16-bit integer

0010

x2

 

 

 

24-bit integer

0011

x3

 

 

 

32-bit integer

0100

x4

 

 

 

32-bit real

0101

x5

 

 

 

48-bit integer

0110

x6

 

 

 

64-bit integer

0111

x7

 

 

 

Variable length

1101

xD

 

 

 

Data function types used by the meter (DIF bits 5-4)

Function type

bin

 

 

Instantaneous

00

 

 

Maximum

01

 

 

Primary VIF used by the meter

NOTE: E denotes the extension bit; x in the hex value is determined by bits 7-4 of the VIF.

Primary VIF

bin

hex

Description

 

 

 

 

Energy

E000 0011

x3

Wh with a resolution of 100

Power

E000 1110

xE

kW with a resolution of 103

Time point

E110 1101

xD

Date and time in data type F, as detailed in the M-Bus

protocol documentation

 

 

 

Bus address

E111 1010

xA

Data type C (unsigned integer), as detailed in the M-Bus

protocol documentation

 

 

 

Primary VIFE

1111 1101

FD

Indicates that the first VIFE is a primary VIF extension

 

 

 

 

Manufacturer-specific VIFE

1111 1111

FF

Indicates that the next VIFE is manufacturer specific

 

 

 

 

Primary VIFE codes used by the meter

The primary VIFE codes in the table below are used by the meter when the VIF equals FD hex (1111 1101 bin).

NOTE: E denotes the extension bit; x in the hex value is determined by bits 7-4 of the VIFE.

Primary VIFE codes

bin

hex

Additional information

 

 

 

 

Manufacturer

E000 1010

xA

Model

E000 1100

xC

Voltage

E100 1001

x9

Volts with a resolution of 100

Current

E101 1100

xC

Amps with a resolution of 100

Digital output

E001 1010

xA

Digital input

E001 1011

xB