Page 67
Image 67
Basic information and meter configuration

iEM3100 / iEM3200 / iEM3300 series user manual

Communications via LonWorks

 

 

Meter status information

You can read the following network variables to obtain configuration and status information about the meter. For information on configuring the meter, see the sections on meter configuration properties and the LonWorks plug-in.

Network variable label

SNVT / UCPT type

Description

 

 

 

 

Basic information and meter configuration

 

 

nvoDateTime

SNVT_time_stamp

Meter date and time (DD/MM/YYYY hh:mm:ss)

 

 

 

nvoOpTimer

SNVT_count_32

Meter operation timer: the time in seconds since the meter was last

powered up

 

 

System configuration information

 

 

 

 

Power system configuration:

 

 

0

= 1PH2W L-N

 

 

1

= 1PH2W L-L

nciSystemType

SNVT_count

2

= 1PH3W L-L with N

 

 

3

= 3PH3W

 

 

11 = 3PH4W

 

 

13 = 1PH4 wire multi L-N

nciWireNum

SNVT_count

Number of wires

2, 3, 4

 

 

 

 

 

nciPhaseNum

SNVT_count

Number of phases

1, 3

 

 

 

 

 

 

 

Number of CTs

nciCtNum

SNVT_count

1, 2, 3

 

 

NOTE: only applies to the iEM3275

 

 

Number of VTs

nciVtNum

SNVT_count

0-10

 

 

NOTE: only applies to the iEM3275

nciVtPrimary

SNVT_count_32

VT Primary

NOTE: only applies to the iEM3275

 

 

nciVTSecondary

SNVT_count

VT Secondary

NOTE: only applies to the iEM3275

 

 

nciCtPrimary

SNVT_count

CT Primary

NOTE: only applies to the iEM3275

 

 

nciCtSecondary

SNVT_count

CT Secondary

NOTE: only applies to the iEM3275

 

 

 

 

VT connection type

nciVtConnType

SNVT_count

0

= Direct connection, no VTs

1

= 3PH3W (2VTs)

 

 

 

 

2

= 3PH4W (3VTs)

 

 

 

nciNominalFreq

SNVT_freq_hz

System frequency

50, 60

 

 

 

 

 

Digital input configuration and status information

 

 

Digital input control mode

 

 

0

= Normal (input status)

nciDICtrMode

SNVT_count

2

= Multi Tariff control

 

 

3

= Input metering

 

 

5

= All partial energy reset (configure to reset all partial energy logs)

 

 

 

nciDIPulseConst

SNVT_count_32

Pulse constant (pulses/unit)

 

 

 

 

 

Digital input status (only Bit 1 is used)

 

 

0

= relay open

nvoDIStatus

SNVT_count

1

= relay closed

 

 

NOTE: The information provided by this variable only applies if the

 

 

digital input control mode is set to Input Status.

Alarm status

 

 

 

 

 

Alarm status (only Bit 1 is used)

nvoAlmStatus

SNVT_count

0

= Alarm is inactive

 

 

1

= Alarm is active

 

 

 

 

DOCA0005EN-04

67

Page 67
Image 67
Schneider Electric iEM3200, iEM3300, iEM3100 user manual Communications via LonWorks, DOCA0005EN-04, Network variable label