Hardware and installation

 

 

Digital input wiring: iEM3135 / iEM3155 / iEM3165 / iEM3175 / iEM3235 / iEM3255 / iEM3265 / iEM3275 / iEM3335 / iEM3355 / iEM3365 / iEM3375

11 – 40 V DC

-

+

 

 

C/- DI

N.C.

• The digital input and output are electrically independent.

Digital output wiring: iEM3135 / iEM3155 / iEM3165 / iEM3235 / iEM3255 / iEM3265 / iEM3335 / iEM3355 / iEM3365

5 – 40 V DC

-/+

 

+/-

 

 

Load

C

DO

N.C.

The programmable digital output is compatible with S0 format when configured as a pulse output.

The digital output is polarity-independent.

The digital input and output are electrically independent.

Modbus RS-485 communications wiring: iEM3150 / iEM3155 / iEM3250 / iEM3255 / iEM3350 / iEM3355

Manual background 0 V

D0 = A’ / Rx-, A / Tx-

D1 = B’ / Rx+, B / Tx+

0V Manual background D0/- D1/+

BACnet RS-485 communications wiring: iEM3165 / iEM3265 / iEM3365

Manual background 0 V

D0 = A’ / Rx-, A / Tx-

D1 = B’ / Rx+, B / Tx+

0V Manual background D0/- D1/+

M-Bus communications wiring: iEM3135 / iEM3235 / iEM3335

The M-Bus communications connection is polarity-independent.

DOCA0005EN-04