iEM3100 / iEM3200 / iEM3300 series user manual

 

 

 

Communications via Modbus RS-485

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Energy values – 32-bit floating point

 

 

 

 

 

 

 

 

Register

Action

Size

Type

Units

Description

 

Address

(R/W/WC)

 

 

 

 

 

 

 

 

Total Energy (cannot be reset)

 

 

 

 

 

 

 

 

 

 

45100

R

2

Float32

Wh

Total Active Energy Import

 

 

 

 

 

 

 

 

45102

R

2

Float32

Wh

Total Active Energy Export

 

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45104

R

2

Float32

VARh

Total Reactive Energy Import

 

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

45106

R

2

Float32

VARh

Total Reactive Energy Export

 

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Partial Energy

 

 

 

 

 

 

 

 

 

 

 

 

45108

R

2

Float32

Wh

Partial Active Energy Import

 

45110

R

2

Float32

VARh

Partial Reactive Energy Import

 

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Phase Energy

 

 

 

 

 

 

 

 

 

 

 

 

45112

R

2

Float32

Wh

Active Energy Import Phase 1

 

45114

R

2

Float32

Wh

Active Energy Import Phase 2

 

45116

R

2

Float32

Wh

Active Energy Import Phase 3

 

Input Metering Counter

 

 

 

 

 

 

 

 

 

 

 

45118

R

2

Float32

Unit

Input Metering Accumulation

 

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

Energy by Tariff (iEM3155 / iEM3255 / iEM3355 only)

 

 

 

 

 

 

 

 

45120

R

2

Float32

Wh

Rate A Active Energy Import

 

 

 

 

 

 

 

 

45122

R

2

Float32

Wh

Rate B Active Energy Import

 

 

 

 

 

 

 

 

45124

R

2

Float32

Wh

Rate C Active Energy Import

 

 

 

 

 

 

 

 

45126

R

2

Float32

Wh

Rate D Active Energy Import

 

 

 

 

 

 

 

 

Overload Alarm (iEM3155 / iEM3255 / iEM3355)

 

 

 

 

 

 

 

 

Register

Action

Size

Type

Units

Description

 

Address

(R/W/WC)

 

 

 

 

 

 

Overload Alarm Setup:

 

45001

R/WC

1

Bitmap

0x0000 = Disabled

 

 

 

 

 

 

0x0100 = Enabled

 

45002

R/WC

2

Float32

kW

Pickup Setpoint

 

 

 

 

 

 

Digital Output to Associate:

 

45004

R/WC

1

Bitmap

0x0000 = Digital Output unassociated to overload alarm

 

 

 

 

 

 

0x0100 = Digital Output associated to overload alarm

 

 

 

 

 

 

Activated Status:

 

45005

R

1

Bitmap

0x0000 = Alarm is inactive

 

 

 

 

 

 

0x0100 = Alarm is active

 

 

 

 

 

 

Unacknowledged Status:

 

45006

R

1

Bitmap

0x0000 = Historic alarm is acknowledged by the user

 

 

 

 

 

 

0x0100 = Historic alarm is unacknowledged by the user

 

45007

R

4

DATETIME

Last Alarm - Time Stamp

 

45011

R

2

Float32

kW

Last Alarm - Value

 

 

 

 

 

 

 

Read Device Identification

The meters supports the Read Device Identification function with the mandatory objects

VendorName, ProductCode and Revision Number.

DOCA0005EN-04

61

Page 61
Image 61
Schneider Electric iEM3200, iEM3300, iEM3100 Read Device Identification, Overload Alarm iEM3155 / iEM3255 / iEM3355