iEM3100 / iEM3200 / iEM3300 series user manualCommunications via LonWorks

Basic setup

Function profile

UCPT

Struct Members

Range / options

Description

 

 

 

 

 

 

 

 

 

 

0

= 1PH2W L-N

 

 

 

 

1

= 1PH2W L-L

 

 

SystemType

0, 1, 2, 3, 11, 13

2

= 1PH3W L-L with N

 

 

3

= 3PH3W

 

 

 

 

 

 

 

 

11 = 3PH4W

 

 

 

 

13 = 1PH4 wire multi L with N

 

 

 

 

 

 

 

NominFreq

50, 60

Nominal frequency in Hz

 

 

 

 

 

 

 

 

 

The minimum value for VtPrimary

nciCfgWiring

UCPTWiring

VtPrimary

0 - 1000000.0

must be equal to or greater than

 

 

the value set for VtSecondary.

 

 

VtSecondary

100, 110, 115, 120

 

 

 

 

 

 

 

CtNum

1, 2, 3

 

 

 

 

 

 

 

CtPrimary

1 - 32767

 

 

 

 

 

 

 

CtSecondary

1, 5

 

 

 

 

 

 

 

 

 

VT connection type

 

 

VtConnType

0, 1, 2

0

= Direct connection

 

 

1

= 3PH3W (2VTs)

 

 

 

 

 

 

 

 

2

= 3PH4W (3VTs)

 

 

 

 

 

 

Digital input setup

 

 

 

 

Function profile

UCPT

Struct Members

Range / options

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Associates the digital input to reset partial

 

 

 

 

 

 

energy data:

 

 

 

 

 

 

0 = Digital input is not associated with the

 

 

 

 

 

 

partial energy reset.

nciCfgDigitInpt

UCPTDigitalInput

0, 1

1 = Digital input is associated with the partial

energy reset.

 

 

 

 

 

 

 

 

 

 

 

 

Setting this property to 1 also updates

 

 

 

 

 

 

nciDICtrlMode (UCPTDiCtrlMode) to All

 

 

 

 

 

 

Energy Reset.

Input metering setup

 

 

 

 

 

 

 

 

 

 

 

 

Function profile

UCPT

 

Struct Members

Range / options

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sets the pulse weight (1 - 10000 ms)

 

 

 

PulseWeight

 

1 - 10000

 

Setting this property also sets

 

 

 

 

 

 

 

nciDIPulseConst (UCPTDiPulseConst) to

 

 

 

 

 

 

 

the same value.

 

 

 

 

 

 

 

Associates the digital input with input

 

 

 

 

 

 

 

metering:

nciCfgInptMetAcc

UCPTInputMetering

 

 

 

 

0 = Digital input is not associated with input

 

 

 

 

metering.

 

 

 

 

 

 

 

 

 

 

DigitalAssociation

 

0, 1

 

1 = The digital input is associated with input

 

 

 

 

 

metering.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting this property to 1 also updates

 

 

 

 

 

 

 

nciDICtrlMode (UCPTDiCtrlMode) to Input

 

 

 

 

 

 

 

Metering.

DOCA0005EN-04

69