Telegram information for data records

iEM3100 / iEM3200 / iEM3300 series user manual

Communications via M-Bus

 

 

Telegram information for data records

The following sections outline the telegram information used in data records. The tables contain the following information (if applicable):

Data format in hex (for example, 16-bit integer)

Primary VIF in hex

Primary VIFE codes in bin and hex

Manufacturer-specific VIFE codes in bin and hex

Meter information

NOTE: E denotes the extension bit; the hex value assumes E = 0.

Data format

Primary VIF Extension

 

Description

 

 

 

bin

hex

 

 

 

 

 

 

 

 

0D

E000 1010

0A

Manufacturer

18-bit ASCII = Schneider Electric

 

 

 

 

 

 

 

0D

E000 1100

0C

Model

 

 

 

 

 

 

 

Meter error codes:

 

 

 

0

= Code 101: EEPROM error

 

 

 

1

= Code 102: No calibration table

 

 

 

2 = Code 201: Mismatch between frequency settings and frequency measurements

 

 

 

3

= Code 202: Mismatch between wiring settings and wiring inputs

03

E0001 0111

17

4

= Code 203: Phase sequence reversed

5

= Code 204: Total active energy negative due to incorrect voltage or current

 

 

 

 

 

 

connections

 

 

 

6

= Code 205: Date and time are reset due to a power failure

 

 

 

7

= Code 206: Pulse missing due to overspeed of energy pulse output

 

 

 

8

= Code 207: Abnormal internal clock function

 

 

 

9

= Internal data bus communications error

 

 

 

 

 

Related topics

See “Troubleshooting” on page 103 for more information on the diagnostics codes.

Energy and energy by tariff measurements

The energy and energy by tariff measurements listed below are preserved through power failures. NOTE: E denotes the extension bit; the hex value assumes E = 0.

Data format

DIFE

Primary VIF

Primary VIFE

Manufacturer-specific VIFE

 

Description

 

 

 

 

 

bin

hex

bin

hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

07

03

Total active energy import

07

83

E000 1001

09

Total active energy export

87

40

03

Total reactive energy import

87

40

83

E000 1001

09

Total reactive energy export

07

83

E000 1101

0D

Partial active energy import

87

40

83

E000 1101

0D

Partial reactive energy import

07

83

E000 0001

01

Active energy import phase 1

07

83

E000 0010

02

Active energy import phase 2

07

83

E000 0011

03

Active energy import phase 3

 

 

 

 

 

 

 

Active tariff

 

 

 

 

 

 

 

0

= Multi Tariff feature is disabled

03

E001 0000

10

1

= rate A (tariff 1) active

2

= rate B (tariff 2) active

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

= rate C (tariff 3) active

 

 

 

 

 

 

 

4

= rate D (tariff 4) active

 

 

 

 

 

 

 

 

87

10

03

Rate A (tariff 1) active energy import

 

 

 

 

 

 

 

 

87

20

03

Rate B (tariff 2) active energy import

 

 

 

 

 

 

 

 

87

30

03

Rate C (tariff 3) active energy import

 

 

 

 

 

 

 

 

 

DOCA0005EN-04

79

Page 79
Image 79