Schneider Electric iEM3300, iEM3200, iEM3100 BACnet communications implementation, Related topics

Models: iEM3100 iEM3200 iEM3300

1 112
Download 112 pages 230 b
Page 90
Image 90
BACnet communications implementation

Communications via BACnet

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

 

 

 

 

 

 

 

BACnet component

Description

 

 

 

 

 

 

 

DS-RP-B (Data Sharing - Read Property - B)

 

 

 

DS-RPM-B (Data Sharing - Read Property Multiple - B)

 

 

 

DS-WP-B (Data Sharing - Write Property - B)

 

 

BACNet Interoperability Building Blocks (Annex K)

DS-COV-B (Data Sharing - COV - B)

 

 

 

DM-DDB-B (Device Management - Dynamic Device Binding - B)

 

 

 

DM-DOB-B (Device Management - Dynamic Object Binding - B)

 

 

 

DM-DCC-B (Device Management - Device Communication Control - B)

 

 

Data link layer options

MS/TP master (clause 9)

 

 

Baud rates 9600, 19200, 38400, 57600, 76800

 

 

 

 

 

 

 

 

 

Character set

ANSI X3.4

 

 

 

 

 

 

 

subscribeCOV

 

 

 

readProperty

 

 

 

readPropertyMultiple

 

 

 

writeProperty

 

 

 

deviceCommunicationControl

 

 

Supported services

who-HAS

 

 

 

who-Is

 

 

 

I-Am

 

 

 

I-Have

 

 

 

Confirmed COV notification

 

 

 

Unconfirmed COV notification

 

 

 

 

 

 

Segmentation

The meter does not support segmentation

 

 

 

 

 

 

Static device address binding

The meter does not support static device address binding

 

 

 

 

 

 

Networking options

None

 

 

 

 

 

The following standard object types are supported:

Object type

Optional properties supported

Writable properties supported

Proprietary properties

 

 

 

 

 

Max_Master

Object_Name

 

 

Max_Info_Frames

 

 

Max_Master

 

 

Description

 

 

Max_Info_Frames

ID_800

 

Location

Device Object

Description

ID_801

Local_Date

 

Location

ID_802

 

Local_Time

 

APDU_Timeout

 

 

Active_COV_Subscriptions

 

 

Number_Of_APDU_Retries

 

 

Profile Name

 

 

 

 

 

 

 

 

Analog Input Object

COV_Increment

COV_Increment

 

 

 

 

Analog Value Object

Present_Value

 

 

 

 

Binary Input Object

 

 

 

 

Related topics

See “Device object” on page 91 for information on the proprietary properties in the Device object.

BACnet communications implementation

Configuring basic communication parameters

Before communicating with the meter via BACnet protocol, use the front panel to configure the following settings:

Setting

Possible values

 

 

 

9600

 

19200

Baud rate

38400

 

57600

 

76800

 

 

 

Mac Address

1

- 127

 

 

 

Device ID

0

- 4194303

 

 

 

90

DOCA0005EN-04

Page 90
Image 90
Schneider Electric iEM3300, iEM3200, iEM3100 user manual BACnet communications implementation, Related topics