Schneider Electric iEM3100, iEM3300 Section, Parameter, Options, Description, DOCA0005EN-04

Models: iEM3100 iEM3200 iEM3300

1 112
Download 112 pages 230 b
Page 41
Image 41
Section

iEM3100 / iEM3200 / iEM3300 series user manual

Front panel display and meter setup

 

 

Configuration menu for iEM3100 / iEM3110 / iEM3115 / iEM3300 / iEM3310

Wiring

 

 

Type

 

 

 

 

 

Frequency

 

 

 

Frequency

 

 

 

 

 

 

 

Date

 

 

 

Date

 

 

 

 

 

 

 

Time

 

 

 

Time

 

 

 

 

 

 

 

Pulse Output

 

 

Pulse Constant

 

 

 

 

 

 

 

 

 

 

Pulse Width

 

 

Multi Tariffs

 

 

Control mode

 

 

 

 

 

 

 

 

 

 

Disable

 

 

 

 

 

 

by Internal Clock

 

Schedule

 

 

 

 

 

 

 

 

 

by Digital Input

 

by 2 Tariffs

 

 

 

 

by Communications

 

by 3 Tariffs

 

 

 

 

 

 

by 4 Tariffs

Contrast

 

 

 

Contrast

 

 

 

 

 

 

 

AiEM3110 / iEM3115 / iEM3310

BiEM3110 / iEM3310

CiEM3115

Password

 

Password

 

Reset Config

 

Reset Config

 

Section

Parameter

Options

Description

 

 

 

 

 

 

3PH3W

 

 

 

3PH4W

 

Wiring

Type

1PH2W L-N

Select the power system type the meter is wired to.

 

 

1PH2W L-L

 

 

 

1PH3W L-L-N

 

 

 

 

 

Frequency

Frequency

50

Select the frequency of the electrical power system, in Hz.

60

 

 

 

Date (iEM3110 / iEM3115 /

Date

DD-MMM-YYYY

Set the current date using the specified format.

iEM3310)

 

 

 

Time (iEM3110 / iEM3115 /

Time

hh:mm

Use the 24-hour format to set the time.

iEM3310)

 

 

 

 

 

100

 

 

 

200

 

 

Pulse Constant

1000

Set the pulses per kWh for the pulse output.

 

(imp/kWh)

1

 

 

Pulse Output

 

10

 

 

20

 

 

 

 

 

 

50

 

 

Pulse Width

100

Set the pulse width (ON time).

 

(ms)

200

 

 

 

 

300

 

 

 

 

Select the tariff control mode:

 

 

 

• Disable: the Multi Tariff function is disabled.

 

 

Disable

• by Digital Input: the digital input is associated with the multi-tariff function. A

 

 

signal to the digital input changes the active tariff.

Multi Tariffs (iEM3115)

Control Mode

by Digital Input

• by Internal Clock: the device clock controls the active tariff. If you set the

 

 

by Internal Clock

Control Mode to by Internal Clock, you must also configure the schedule.

 

 

 

Set the time when each tariff period starts, using the 24 hour clock format

 

 

 

(00:00 to 23:59). The start time of the next tariff is the end time of the current

 

 

 

tariff. For example, T2 start equals the end of T1.

Contrast

Contrast

1-9

Increase or decrease the value to increase or decrease the display contrast.

Password

 

 

 

(iEM3110 / iEM3115 /

Password

0-9999

Sets the password for accessing the meter configuration screens and resets.

iEM3310)

 

 

 

Reset Config

Reset Config

Settings are reset to their defaults, except for Password. Meter restarts.

 

 

 

 

DOCA0005EN-04