Schneider Electric iEM3100 Analog Value object, Binary Input objects, Communications via BACnet

Models: iEM3100 iEM3200 iEM3300

1 112
Download 112 pages 230 b
Page 95
Image 95
Analog Value object

iEM3100 / iEM3200 / iEM3300 series user manual

Communications via BACnet

 

 

Analog Value object

There is one Analog Value (AV) object available on the meter, named AV00 - Command. The available commands are listed in the following table. Enter the number in the Present_Value column in the Present_Value property of the AV object to write the associated command to the meter.

Command

Present_Value entry

Object name / description

 

 

 

 

 

Acknowledge an overload alarm.

Acknowledge Overload Alarm

20001.00

The alarm indicator disappears from the front panel display after you

 

 

acknowledge the alarm; however, this does not address the state that

 

 

caused the alarm.

 

 

Reset partial energy accumulation to 0.

Reset Partial Energy Counter

2020.00

Partial Active / Reactive Energy, Energy by Tariff and Phase Energy

 

 

registers are reset.

Reset Input Metering Counter

2023.00

Resets input metering accumulation to 0.

 

 

 

Binary Input objects

The following table lists the Binary Input (BI) objects available on the meter.

NOTE: The Value Type for all BI objects is Boolean.

Object ID

Object name / description

 

 

 

BI00 - Digital Output Enable

0

Indicates whether or not the digital output functions as an energy pulse output:

0

= Digital output disabled

 

 

1

= Digital output is associated with active energy pulse output

 

 

 

BI01 - Digital Input Association Enable

1

Indicates whether or not the digital input is associated with input metering:

0

= Digital input is not associated with input metering.

 

 

1

= Digital input is associated with input metering.

 

 

 

BI02 - Digital Input Status

2

0

= relay open

1

= relay closed

 

 

NOTE: This information only applies if the digital input is set to Input Status.

 

BI03 - Alarm Enable

3

Indicates whether the overload alarm is enabled or disabled:

0

= disabled

 

 

1

= enabled

 

 

 

BI04 - Digital Output Association Enable

4

Indicates if the digital output is configured for alarming:

0

= digital output disabled

 

 

1

= for Alarm (digital output is associated with the overload alarm)

 

 

 

BI05 - Alarm Status

5

0

= Alarm is inactive

 

1

= Alarm is active

 

BI06 - Unacknowledged status

6

0

= historic alarm is acknowledged

 

1

= historic alarm is unacknowledged

 

 

 

DOCA0005EN-04

95

Page 95
Image 95
Schneider Electric iEM3100, iEM3300 Analog Value object, Binary Input objects, Communications via BACnet, DOCA0005EN-04