iEM3100 / iEM3200 / iEM3300 series user manual

Hardware and installation

 

 

Power system

 

 

 

 

 

Wiring

 

 

 

 

 

N

N’ L1 L1’ L2

L2’

L3

L3’

N

N’ L1 L1’ L2

L2’

L3

L3’

 

L1

 

 

 

 

L1

 

 

 

 

3PH4W

L2

 

 

 

 

L2

 

 

 

 

 

L3

 

 

 

 

L3

 

 

 

 

 

N

≤277 V L-N

 

 

 

N

≤277 V L-N

 

 

 

 

 

 

 

 

 

 

 

 

≤480 V L-L

≤480 V L-L

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Do not connect N’ to the load when setting the wiring type on the meter to 1PH4W Multi L-N.

Failure to follow these instructions will result in death or serious injury.

Power system

 

 

Wiring

 

 

N

N’

L1

L1’ L2 L2’

L3

L3’

1PH multiple loads with neutral (1PH4W Multi L-N)1

 

 

 

 

 

1The 1PH4W Multi L-N wiring type is only available on the iEM3335, iEM3350, iEM3355, iEM3365 and iEM3375.

5 A / 1 A meter wiring

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Never short the secondary of a voltage transformer (VT).

Never open circuit a current transformer (CT); use the shorting block to short circuit the leads of the CT before removing the connection from the meter.

Always use grounded external CTs for current inputs.

Failure to follow these instructions will result in death or serious injury.

Single-phase systems with CTs

 

 

 

 

250 mA fuses and disconnect switch

 

 

 

 

Shorting block

 

 

 

 

Power system

 

Wiring

 

 

V1 V2 V3Vn

(I1)

(I2)

(I3)

 

 

 

 

1PH2W L-N

 

 

 

 

 

 

S1

S2

 

 

 

≤277 V L-N

 

DOCA0005EN-04

29

Page 29
Image 29
Schneider Electric iEM3100 a meter wiring, Single-phase systems with CTs, MA fuses and disconnect switch Shorting block