Instantaneous (RMS) measurements

Communications via LonWorks

 

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

 

 

 

 

 

 

 

Network variable label

Type

Description

 

 

 

 

 

nvoPh1kWh

SNVT_elec_kwh_l

Active energy import phase 1

 

nvoPh2kWh

SNVT_elec_kwh_l

Active energy import phase 2

 

nvoPh3kWh

SNVT_elec_kwh_l

Active energy import phase 3

 

nvoPh1Wh

SNVT_elec_whr_f

Active energy import phase 1

 

nvoPh2Wh

SNVT_elec_whr_f

Active energy import phase 2

 

nvoPh3Wh

SNVT_elec_whr_f

Active energy import phase 3

 

 

 

Active tariff

 

 

 

0 = Multi Tariff feature is disabled

 

nvoTariffActRate

SNVT_count

1 = rate A (tariff 1) active

 

2 = rate B (tariff 2) active

 

 

 

 

 

 

3 = rate C (tariff 3) active

 

 

 

4 = rate D (tariff 4) active

 

 

 

 

 

nvoTariffAkWh

SNVT_elec_kwh_l

Rate A (tariff 1) active energy import

 

 

 

 

 

nvoTariffBkWh

SNVT_elec_kwh_l

Rate B (tariff 2) active energy import

 

 

 

 

 

nvoTariffCkWh

SNVT_elec_kwh_l

Rate C (tariff 3) active energy import

 

 

 

 

 

nvoTariffDkWh

SNVT_elec_kwh_l

Rate D (tariff 4) active energy import

 

 

 

 

 

nvoTariffAWh

SNVT_elec_whr_f

Rate A (tariff 1) active energy import

 

 

 

 

 

nvoTariffBWh

SNVT_elec_whr_f

Rate B (tariff 2) active energy import

 

 

 

 

 

nvoTariffCWh

SNVT_elec_whr_f

Rate C (tariff 3) active energy import

 

 

 

 

 

nvoTariffDWh

SNVT_elec_whr_f

Rate D (tariff 4) active energy import

 

 

 

 

 

nvoInMeterAcc

SNVT_count_f

Input metering accumulation

 

 

 

 

 

nvoRstEnergyDT

SNVT_time_stamp

Date and time of last energy reset

 

 

 

 

Related topics

See “Resets” on page 68 for information on resetting values.

See “Network propagation rate setup” on page 70 for information on variables that control the network update rate.

Instantaneous (RMS) measurements

Network variable label

Type

Description

 

 

 

nvoActPowerPh1

SNVT_power_f

Active power Phase 1

nvoActPowerPh2

SNVT_power_f

Active power Phase 2

nvoActPowerPh3

SNVT_power_f

Active power Phase 3

nvoActPowerSum

SNVT_power_f

Total active power

nvoRctPowerSum

SNVT_power_f

Total reactive power

nvoAppPowerSum

SNVT_power_f

Total apparent power

nvoVoltsL1N

SNVT_volt_f

Voltage L1-N

nvoVoltsL2N

SNVT_volt_f

Voltage L2-N

nvoVoltsL3N

SNVT_volt_f

Voltage L3-N

nvoVoltsLNAvg

SNVT_volt_f

Average voltage line-to-neutral

nvoVoltsL1L2

SNVT_volt_f

Voltage L1-L2

nvoVoltsL2L3

SNVT_volt_f

Voltage L2-L3

nvoVoltsL3L1

SNVT_volt_f

Voltage L3-L1

nvoVoltsLLAvg

SNVT_volt_f

Average voltage line-to-line

nvoCurrentPh1

SNVT_amp_f

Phase 1 current

nvoCurrentPh2

SNVT_amp_f

Phase 2 current

nvoCurrentPh3

SNVT_amp_f

Phase 3 current

nvoCurrentAvg

SNVT_amp_f

Average current

nvoAvgPwrFactor

SNVT_count_inc_f

Total power factor

nvoFrequency

SNVT_freq_f

Frequency

Related topics

See “Network propagation rate setup” on page 70 for information on variables that control the network update rate.