Communications via Modbus RS-485

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

Modbus functions

Function list

The table below lists the supported Modbus functions:

Function code

Function name

 

 

Decimal

Hexadecimal

 

 

 

 

3

0x03

Read Holding Registers

 

 

 

16

0x10

Write Multiple Registers

 

 

 

43/14

0x2B/0x0E

Read Device Identification

 

 

 

For example:

To read different parameters from the meter, use function 3 (Read).

To change the tariff, use function 16 (Write) to send a command to the meter.

Table format

Register tables have the following columns:

Register Address

Action (R/W/WC)

 

 

Size

Type

Units Range

Description

Register Address: Modbus address of register encoded in the Modbus frame, in decimal (dec)

Action: The read/write/write by command property of the register

Size: The data size in Int16

Type: The encoding data type

Units: The unit of the register value

Range: The permitted values for this variable, usually a subset of what the format allows

Description: Provides information about the register and the values that apply

Unit table

The following data types appear in the Modbus register list:

Type

Description

Range

 

 

 

 

UInt16

16 bit unsigned integer

0

– 65535

Int16

16 bit signed integer

-32768 to +32767

UInt32

32 bit unsigned integer

0

– 4 294 967 295

Int64

64 bit unsigned integer

0

– 18 446 744 073 709 551 615

UTF8

8 bit field

multibyte character encoding for Unicode

Float32

32 bit value

Standard representation IEEE for floating number (with single precision)

Bitmap

DATETIME

See below

52

DOCA0005EN-04

Page 52
Image 52
Schneider Electric iEM3200, iEM3300, iEM3100 user manual Modbus functions, Function list, Table format, Unit table