Front panel display and meter setup |
| iEM3100 / iEM3200 / iEM3300 series user manual | ||
|
|
|
| |
|
|
|
| |
Section | Parameter | Options | Description | |
|
|
|
| |
|
|
| Select the tariff control mode: | |
|
|
| • Disable: the Multi Tariff function is disabled. | |
|
| Disable | • by Communication: the active tariff is control by communications. See | |
|
| the chapter for the applicable protocol for more information. | ||
|
|
| ||
Multi Tariffs | Control Mode | by Communication | • by Digital Input: the digital input is associated with the | |
by Digital Input | function. A signal to the digital input changes the active tariff. | |||
|
| • by Internal Clock: the device clock controls the active tariff. If you set the | ||
|
| by Internal Clock | ||
|
| Control Mode to by Internal Clock, you must also configure the | ||
|
|
| schedule. Set the time when each tariff period starts, using the 24 hour | |
|
|
| clock format (00:00 to 23:59). The start time of the next tariff is the end | |
|
|
| time of the current tariff. For example, T2 start equals the end of T1. | |
|
| Disable | Select whether or not the Overload Alarm is enabled: | |
Overload Alarm | Alarm | • Disable: the alarm is disabled. | ||
Enable | ||||
|
| • Enable: the alarm is enabled. If you enabled the Overload Alarm, you | ||
|
|
| must also configure the Pick Up Value in kW from 1 - 9999999. | |
|
|
| Select how the digital output functions: | |
|
|
| • Disable: the digital output is disabled. | |
|
|
| • for Alarm: the digital output is associated with the overload alarm. The | |
|
| Disable | meter sends a pulse to the digital output port when the alarm is | |
Digital Output | DO Function | for Alarm | triggered. | |
• for Pulse: The digital output is associated with energy pulsing. When | ||||
|
| for Pulse (kWh) | ||
|
| this mode is selected, you must also configure the can select the energy | ||
|
|
| parameter and the set the Pulse Constant (imp/kWh) and the Pulse | |
|
|
| Width (ms). | |
|
|
| NOTE: the iEM3175 and iEM3375 do not have a digital output. | |
|
|
| Select how the digital input functions: | |
|
|
| • Input status: the digital input records the status of the input, for example, | |
|
| Input Status | OF, SD of a circuit breaker. | |
|
| Tariff Control | • Input Metering: the digital input is associated with input metering. The | |
Digital Input | DI Function | meter counts and records the number of incoming pulses. If you set the | ||
Input Metering | ||||
|
| DI Function to Input Metering, you must also configure In. Pulse | ||
|
| Partial Reset | Constant. | |
|
| • Tariff Control: the digital input is associated with the | ||
|
|
| ||
|
|
| A signal to the digital input changes the active tariff. | |
|
|
| • Partial Reset: a signal to the digital input initiates a partial reset. | |
| Slave Address | 1 - 247 | Set the address for this device. The address must be unique for each | |
| device in a communications loop. | |||
|
|
| ||
|
| 19200 | Select the speed for data transmission. The baud rate must be the same for | |
Communication | Baud Rate | 38400 | ||
all devices in a communications loop. | ||||
(iEM3155 / iEM3355) |
| 9600 |
| |
|
| Even | Select None if the parity bit is not used. The parity setting must be the same | |
| Parity | Odd | for all devices in a communications loop. | |
|
| None | NOTE: Number of stop bits = 1. | |
| Primary Addr. | 0 - 255 | Set the address for this device. The address must be unique for each | |
| device in a communications loop. | |||
|
|
| ||
|
| 2400 |
| |
Communication |
| 4800 |
| |
(iEM3135 / iEM3335) | Baud Rate | 9600 | Select the speed for data transmission. The baud rate must be the same for | |
| 300 | all devices in a communications loop. | ||
|
| |||
|
| 600 |
| |
|
| 1200 |
| |
|
|
|
| |
| MAC Addr. | 1 - 127 | Set the address for this device. The address must be unique for each | |
| device in a communications loop. | |||
|
|
| ||
|
| 9600 |
| |
Communication |
| 19200 | Select the speed for data transmission. The baud rate must be the same for | |
Baud Rate | 38400 | |||
(iEM3165 / iEM3365) | all devices in a communications loop. | |||
| 57600 | |||
|
|
| ||
|
| 76800 |
| |
|
|
|
| |
| Device ID | 0 - 4194303 | Set the Device ID for this device. Make sure the Device ID is unique in your | |
| BACnet network. | |||
|
|
| ||
Com.Protection | Com.Protection | Enable | Protects selected settings and resets from configuration via | |
Disable | communications. | |||
|
| |||
|
|
|
| |
Contrast | Contrast | Increase or decrease the value to increase or decrease the display | ||
contrast. | ||||
|
|
| ||
Password | Password | Sets the password for accessing the meter configuration screens and | ||
resets. | ||||
|
|
| ||
Reset Config | Reset Config | — | Settings are reset to their defaults, except for Password. Meter restarts. | |
|
|
|
|
44 |
|