Front panel display and meter setup

 

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

 

 

 

 

 

 

Section

Parameter

Options

Description

 

 

 

 

 

 

 

Select the tariff control mode:

 

 

 

• Disable: the Multi Tariff function is disabled.

 

 

Disable

• by Communication: the active tariff is control by communications. See

 

 

the chapter for the applicable protocol for more information.

 

 

 

Multi Tariffs

Control Mode

by Communication

• by Digital Input: the digital input is associated with the multi-tariff

by Digital Input

function. A signal to the digital input changes the active tariff.

 

 

• by Internal Clock: the device clock controls the active tariff. If you set the

 

 

by Internal Clock

 

 

Control Mode to by Internal Clock, you must also configure the

 

 

 

schedule. Set the time when each tariff period starts, using the 24 hour

 

 

 

clock format (00:00 to 23:59). The start time of the next tariff is the end

 

 

 

time of the current tariff. For example, T2 start equals the end of T1.

 

 

Disable

Select whether or not the Overload Alarm is enabled:

Overload Alarm

Alarm

• Disable: the alarm is disabled.

Enable

 

 

• Enable: the alarm is enabled. If you enabled the Overload Alarm, you

 

 

 

must also configure the Pick Up Value in kW from 1 - 9999999.

 

 

 

Select how the digital output functions:

 

 

 

• Disable: the digital output is disabled.

 

 

 

• for Alarm: the digital output is associated with the overload alarm. The

 

 

Disable

meter sends a pulse to the digital output port when the alarm is

Digital Output

DO Function

for Alarm

triggered.

• for Pulse: The digital output is associated with energy pulsing. When

 

 

for Pulse (kWh)

 

 

this mode is selected, you must also configure the can select the energy

 

 

 

parameter and the set the Pulse Constant (imp/kWh) and the Pulse

 

 

 

Width (ms).

 

 

 

NOTE: the iEM3175 and iEM3375 do not have a digital output.

 

 

 

Select how the digital input functions:

 

 

 

• Input status: the digital input records the status of the input, for example,

 

 

Input Status

OF, SD of a circuit breaker.

 

 

Tariff Control

• Input Metering: the digital input is associated with input metering. The

Digital Input

DI Function

meter counts and records the number of incoming pulses. If you set the

Input Metering

 

 

DI Function to Input Metering, you must also configure In. Pulse

 

 

Partial Reset

Constant.

 

 

• Tariff Control: the digital input is associated with the multi-tariff function.

 

 

 

 

 

 

A signal to the digital input changes the active tariff.

 

 

 

• Partial Reset: a signal to the digital input initiates a partial reset.

 

Slave Address

1 - 247

Set the address for this device. The address must be unique for each

 

device in a communications loop.

 

 

 

 

 

19200

Select the speed for data transmission. The baud rate must be the same for

Communication

Baud Rate

38400

all devices in a communications loop.

(iEM3155 / iEM3355)

 

9600

 

 

 

Even

Select None if the parity bit is not used. The parity setting must be the same

 

Parity

Odd

for all devices in a communications loop.

 

 

None

NOTE: Number of stop bits = 1.

 

Primary Addr.

0 - 255

Set the address for this device. The address must be unique for each

 

device in a communications loop.

 

 

 

 

 

2400

 

Communication

 

4800

 

(iEM3135 / iEM3335)

Baud Rate

9600

Select the speed for data transmission. The baud rate must be the same for

 

300

all devices in a communications loop.

 

 

 

 

600

 

 

 

1200

 

 

 

 

 

 

MAC Addr.

1 - 127

Set the address for this device. The address must be unique for each

 

device in a communications loop.

 

 

 

 

 

9600

 

Communication

 

19200

Select the speed for data transmission. The baud rate must be the same for

Baud Rate

38400

(iEM3165 / iEM3365)

all devices in a communications loop.

 

57600

 

 

 

 

 

76800

 

 

 

 

 

 

Device ID

0 - 4194303

Set the Device ID for this device. Make sure the Device ID is unique in your

 

BACnet network.

 

 

 

Com.Protection

Com.Protection

Enable

Protects selected settings and resets from configuration via

Disable

communications.

 

 

 

 

 

 

Contrast

Contrast

1-9

Increase or decrease the value to increase or decrease the display

contrast.

 

 

 

Password

Password

0-9999

Sets the password for accessing the meter configuration screens and

resets.

 

 

 

Reset Config

Reset Config

Settings are reset to their defaults, except for Password. Meter restarts.

 

 

 

 