Communications settings information

Communications via BACnet

 

 

 

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

 

 

 

 

 

 

 

 

 

 

 

Object ID

Units

Default COV

Object name / description

 

 

 

 

 

 

 

 

54

A

1

AI54 - CT Secondary

 

 

NOTE: only applies to the iEM3265

 

 

 

 

 

 

 

 

 

 

AI55 - VT connection type

 

 

55

1

0

= Direct connection, not VTs

 

 

1

= 3PH3W (2VTs)

 

 

 

 

 

 

 

 

 

 

2

= 3PH4W (3VTs)

 

 

 

 

 

 

 

 

Communications settings information

The following AI objects display information about the meter’s communications settings.

NOTE: You can access the meter’s communications configuration information over BACnet communications. However, you must use the front panel to configure the meter’s settings.

Object ID

Units

Default COV

Object name / description

 

 

 

 

00

1

AI00 - BACnet MAC Address

01

1

AI01 - BACnet Baud Rate

Digital input and output setting information

The following AI objects display information about the meter’s I/O settings.

NOTE: You can access the meter’s I/O configuration information over BACnet communications. However, you must use the front panel to configure the meter’s settings.

Object ID

Units

Default COV

Object name / description

 

 

 

 

 

 

 

AI02 - Pulse Duration

02

ms

1

The energy pulse duration (or pulse width), in milliseconds, of the digital

output.

 

 

 

NOTE: This information only applies if the digital output mode is set to

 

 

 

energy pulsing.

 

 

 

AI03 - Pulse Weight

03

1

The pulses/unit setting of the digital input when it is configured for input

metering.

 

 

 

NOTE: This information only applies if the digital input mode is set to

 

 

 

Input Metering.

 

 

 

AI04 - Pulse Constant

04

1

The pulses/kWh setting of the digital output.

NOTE: This information only applies if the digital output mode is set to

 

 

 

 

 

 

energy pulsing.

 

 

 

AI05 - Digital Input Mode

 

 

 

0 = Normal (input status)

05

1

2 = Multi Tariff control

 

 

 

3 = Input metering

 

 

 

5 = All partial energy logs reset

 

 

 

 

 

 

 

AI06 - Digital Output Mode

06

1

2 = Alarm

3 = Energy

 

 

 

 

 

 

0xFFFF (65535 dec) = Disabled

 

 

 

 

42

kW

10

AI42 - Pickup Setpoint

Active power alarm pickup setpoint in kW

 

 

 

 

 

 

 

43

kW

10

AI43 - Last Alarm Value

 

 

 

 

Related topics

See “Device configuration” on page 38 for information on configuring the meter using the front panel.

See “Binary Input objects” on page 95 for information on reading the statuses of the input, output and alarm.