Schneider Electric iEM3200, iEM3300 Telegram information for meter configuration, Related topics

Models: iEM3100 iEM3200 iEM3300

1 112
Download 112 pages 230 b
Page 82
Image 82
Alarm status information

Communications via M-Bus

 

 

 

 

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data format

Primary VIFE

Manufacturer-specific VIFE

 

Description

 

 

 

 

 

bin

hex

bin

hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pulse weight of the digital output

05

E010 1110

2E

NOTE: This information only applies if the digital output mode is set to

 

 

 

 

 

energy pulsing.

 

 

 

 

 

Digital output control mode

03

E001 1010

1A

2

= for Alarm

3

= for Pulse (kWh)

 

 

 

 

 

 

 

 

 

 

0xFFFF = Disabled

 

 

 

 

 

 

 

 

 

 

 

Digital output association with energy pulsing:

03

E010 1101

2D

0

= Digital output disabled

 

 

 

 

 

1

= for Pulse (digital output is associated with active energy pulse output)

 

 

 

 

 

 

 

 

 

 

 

Digital output association with overload alarm:

02

E011 0110

36

0x0000 = digital output disabled

 

 

 

 

 

0x0100 = for Alarm (digital output is associated with the overload alarm)

Alarm status information

NOTE: E denotes the extension bit; the hex value assumes E = 0.

Data format

Primary VIF

Manufacturer-specific VIFE

 

Description

 

 

 

 

bin

 

hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm status:

02

E011 0111

37

 

0x0000

= Alarm is inactive

 

 

 

 

 

0x0100

= Alarm is active

 

 

 

 

 

 

 

 

 

 

 

Acknowledgement status:

02

E011 1000

38

 

0x0000

= historic alarm is acknowledged by the user

 

 

 

 

 

0x0100

= historic alarm is unacknowledged by the user

04

ED

E011 1001

39

 

Timestamp of last alarm (DD/MM/YYYY hh:mm:ss)

05

E011 1010

3A

 

Value at last alarm

 

 

 

 

 

Overload alarm configuration:

02

E011 0100

34

 

0x0000

= disabled

 

 

 

 

 

0x0100

= enabled

 

 

 

 

 

 

05

E011 0101

35

 

The pickup setpoint in kW for the overload alarm

 

 

 

 

 

 

 

Telegram information for meter configuration

You can use the information provided in this section to write to the meter using a SND_UD function.

NOTE: If Com. Protection is enabled, you may receive an error response when you try to configure the meter over communications.

You can also configure the meter using the M-Bus tool available from www.schneider-electric.com.

Supported VIFE codes for meter configuration

NOTE: E denotes the extension bit; the hex value assumes E = 0.

VIFE code

 

Action

Description

 

 

 

bin

 

hex

 

 

 

 

 

 

 

 

E000 0000

00

 

Write and replace

Replaces the old value with the new value.

 

 

 

 

 

E000 0111

07

 

Clear

Resets an accumulated value to 0 (zero).

 

 

 

 

 

Related topics

See “Configuration mode menus” on page 40 for information on enabling and disabling Com. Protection.

See “M-Bus tool for data display and meter configuration” on page 85 for information on the M-Bus tool.

82

DOCA0005EN-04

Page 82
Image 82