Schneider Electric iEM3200, iEM3300, iEM3100 user manual Danger, A direct measurement meter wiring

Models: iEM3100 iEM3200 iEM3300

1 112
Download 112 pages 230 b
Page 28
Image 28
125 A direct measurement meter wiring

Hardware and installation

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

Manual background DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Do not connect N’ to the load when setting the wiring type on the meter to 1PH4W Multi L-N.

Failure to follow these instructions will result in death or serious injury.

Power system

 

 

Wiring

 

 

N

N’

L1

L1’ L2 L2’

L3

L3’

1PH multiple loads with neutral (1PH4W Multi L-N)1

 

 

 

 

 

1The 1PH4W Multi L-N wiring type is only available on the iEM3135, iEM3150, iEM3155, iEM3165 and iEM3175.

125 A direct measurement meter wiring

Manual background DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Do not allow the total additive current flowing through the device to exceed 125 A.

Failure to follow these instructions will result in death or serious injury.

Manual background Fuses and disconnect switch

Power system

 

 

 

 

 

 

Wiring

 

 

 

 

 

 

 

 

N

N’

L1 L1’ L2

L2’

L3

L3’

 

 

 

N

N’ L1 L1’ L2

L2’

L3

L3’

1PH2W L-N

L

 

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

≤277 V L-N

 

 

 

 

 

N

 

≤277 V L-N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

N’ L1 L1’

L2

L2’ L3

L3’

 

 

 

 

1PH2W L-L

 

 

 

L1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L2

 

 

≤480 V L-L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

N’

L1 L1’ L2

L2’

L3

L3’

 

 

 

N

N’ L1 L1’ L2

L2’

L3

L3’

1PH3W L-L-N

L1

 

 

 

 

 

 

 

L1

 

 

 

 

 

L2

 

 

 

 

 

 

 

L2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

≤277 V L-N

 

 

 

 

N

 

≤277 V L-N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

≤480 V L-L

 

 

 

 

 

 

 

≤480 V L-L

 

 

 

 

 

 

 

 

 

N

N’ L1 L1’

L2

L2’ L3

L3’

 

 

 

 

3PH3W

 

 

 

L1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L3

 

 

≤480 V L-L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

DOCA0005EN-04

Page 28
Image 28
Schneider Electric iEM3200 Danger, A direct measurement meter wiring, Hazard Of Electric Shock, Explosion, Or Arc Flash