8.6 EEV PROGRAMMING

EXPANSION VALVE OPTIONS DISPLAY

When the expansion valve type is set to thermostatic by opening DIP switch #7, the EEV controller, low superheat safety device, low superheat safety and the sensor failure safety will be disabled. The EEV output will be set to 0.

S1 - 7 E X P A N S I O N V A L V E T H E R M O S T A T I C

PROGRAM MODE DISPLAYS

The following value is programmable under the PRO- GRAM key (See Table 2).

·System Suction Superheat Setpoint (9.0°F to 15.0°F) (5.0ºC to 8.3ºC)

S U C T S U P E R H E A T

S E T P O I N T = X X . X º F

8

When the expansion valve type is set to electronic by closing DIP switch #7 , the EEV controller, low superheat safety device, low superheat safety and the sensor failure safety will be enabled.

S1 - 7 E X P A N S I O N V A L V E

T H E R M O S T A T I C

The Expansion Valve type selection is viewable under the OPTIONS key.

TABLE 2 – PROGRAMMABLE VALUES TABLE (MINIMUM/MAXIMUM)

PROGRAM VALUE

MODE

LOW LIMIT

HIGH LIMIT

DEFAULT

SUPERHEAT SETPOINT

EEV

9.0°F

15.0°F

12.0°F

(5.0°C)

(8.3°C)

(6.6°C)

 

 