Technical Data

FORM 201.19-NM1 (204)

ELECTRICAL DATA

OPTIONAL SINGLE-POINT POWER SUPPLY

CONNECTION WITH FIELD SUPPLIED CIRCUIT

PROTECTION

Suitable for:

Y - Start and

Across-The-Line-Start

One field provided power supply circuit to the unit. Field connections to factory provided Non-Fused Disconnect Switch (Opt), or Terminal Block (Opt). Factory connections to Terminal Blocks in each of the two Power Panels.

See page 62 for notes.

LD05550

OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION – 2 COMPRESSOR UNITS

(One Field Provided Power Supply Circuit to the Chiller. Field connections to Factory Provided Terminal Block (Standard) or Non-Fused Disconnect (option).

No Internal Branch Circuit Protection (Breakers) per Motor Control Center10)

CHILLER

 

 

 

 

 

 

 

FIELD-SUPPLIED WIRING

 

 

 

 

FIELD PROVIDED POWER SUPPLY

 

 

 

FACTORY PROVIDED

 

(LUGS) WIRE RANGE 7

MODEL

VOLTS

 

 

 

 

 

YCAS

 

MCA1

MIN NF

OVER-CURRENT

PROTECTION13

 

 

STANDARD

 

OPTIONAL NF

 

DISC SW2, 9

MIN.3, 5

 

MAX.4, 6

 

 

 

 

 

 

 

 

 

TERMINAL BLOCK

 

DISC. SWITCH

0130EC

460

273

400

300

 

350

 

# 1 - 500

 

(2) 3/0-250

575

217

250

250

 

300

 

# 1 - 500

 

# 6 - 350

 

 

 

 

0140EC

460

293

400

350

 

400

 

(2) # 2 - 300

 

(2) 3/0-250

575

234

250

300

 

300

 

# 1 - 500

 

# 6 - 350

 

 

 

 

0150EC

460

307

400

350

 

400

 

(2) # 2 - 300

 

(2) 3/0-250

575

246

400

300

 

300

 

# 1 - 500

 

(2) 3/0-250

 

 

 

 

0160EC

460

320

400

400

 

400

 

(2) # 2 - 300

 

(2) 3/0-250

575

257

400

300

 

350

 

# 1 - 500

 

(2) 3/0-250

 

 

 

 

0170EC

460

335

400

400

 

450

 

(2) # 2 - 300

 

(2) 3/0-250

575

268

400

300

 

350

 

# 1 - 500

 

(2) 3/0-250

 

 

 

 

0180EC

460

347

400

400

 

450

 

(2) # 2 - 300

 

(2) 3/0-250

575

277

400

350

 

350

 

(2) # 2 - 300

 

(2) 3/0-250

 

 

 

 

0200EC

460

375

400

450

 

500

 

(2) # 1 - 500

 

(2) 3/0-250

575

299

400

350

 

400

 

(2) # 2 - 300

 

(2) 3/0-250

 

 

 

 

0210EC

460

393

600

450

 

500

 

(2) # 1 - 500

 

(2) 250-500

575

313

400

350

 

400

 

(2) # 2 - 300

 

(2) 3/0-250

 

 

 

 

0230EC

460

407

600

450

 

500

 

(2) # 1 - 500

 

(2) 250-500

575

324

400

400

 

450

 

(2) # 2 - 300

 

(2) 3/0-250

 

 

 

 

See page 62 for Electrical Data footnotes.

58

YORK INTERNATIONAL

Page 58
Image 58
York YCAS0130 manual Chiller FIELD-SUPPLIED Wiring Field Provided Power Supply