TABLE 14 – ISN OPERATIONAL AND FAULT CODES
P56/58 | C1 Operational Code | P57/59 | C1 Fault Code | |
|
|
|
| |
0 | No Abnormal Condition | 0 | No Fault | |
1 | Unit Switch Off | 1 | VAC Under Voltage | |
2 | System Switch Off | 2 | Low Ambient Temperature | |
3 | Lock - Out | 3 | High Ambient Temperature | |
4 | Unit Fault | 4 | Low Leaving Chilled Liquid Temp | |
5 | System Fault | 5 | High Discharge Pressure | |
6 | Remote Shutdown | 6 | High Differential Oil Pressure | |
7 | Daily Schedule Shutdown | 7 | Low Suction Pressure | |
8 | No Run Permissive | 8 | High Motor Current | |
Flow Switch Open (Euro CAT) | ||||
|
|
| ||
9 | No Cool Load | 9 | LLSV Not On | |
10 | 10 | Low Battery Warning | ||
11 | 11 | High Oil Temperature | ||
12 | Manual Override | 12 | High Discharge Temperature | |
13 | Suction Limiting | 13 | Improper Phase Rotation | |
14 | Discharge Limiting | 14 | Low Motor Current / MP / HPCO | |
15 | Current Limiting | 15 | Motor Current Unbalanced | |
16 | Load Limiting | 16 | Low Differential Oil Pressure | |
17 | Compressor Running | 17 | Ground Fault | |
|
| 18 | MP / HPCO | |
|
| 19 | Low Evaporator Temperature | |
|
| 20 | Incorrect Refrigerant Programmed | |
|
| 21 | Power Failure, Manual reset Required | |
|
| 22 | I/O Board Failure | |
|
| 23 | Low Superheat | |
|
| 24 | Sensor Fault | |
|
| 25 | Reprogram Unit Type | |
|
| 26 | MP / HPCO Inhibit | |
|
| 27 | Heat Recovery Select | |
|
|
|
|
*The operational and fault codes are defined in table 14. Note that this table of fault and operational codes is for all DX products. The codes that are grayed out are not used on this unit.