Error Messages and Error Codes

Error Messages and Error Codes

Error Messages (push-button operation)

Error

Description

Cause

Message

 

 

 

 

• Device is faulty

 

 

• Possible short circuit in the probe or the

Flta

Fault/failure has been detected

device wiring

• Possible fault in the device, or lack of

 

 

 

 

sufficient energy at the device

 

 

terminals

 

 

 

ooLa

 

The product level has risen above the

Output out-of-limits

Upper Sensor LImit, or fallen below the

 

 

Lower Sensor Limit

 

 

 

a.Alternates with the primary variable (PV).

Error Codes (HART)

Error

Description

Cause

Code

 

 

32

program memory checksum error

Device is faulty

 

 

 

16

signal error: the measurement

Possible short circuit in the probe or the device

circuitry stopped functioning

wiring

 

 

DAC drive failure: the current as

Possible fault in the device, or lack of sufficient

8

set by the DAC does not match

energy at the device terminals

 

the value measured by the ADC

 

 

 

 

 

 

PV value is outside the limits set

Usually indicates a fault in the connection

0

between the transmitter module and the probe

(USL and LSL)

 

(the coaxial connector is off)

 

 

 

 

 

7ML19985GE01

SITRANS LC 500 – INSTRUCTION MANUAL

Page 53

Troubleshooting

Page 59