Siemens LC 500 Analog Signalling Mode 2-state menu level, Appendix A, Menu, Affected, Description

Models: Sitrans

1 122
Download 122 pages 51.76 Kb
Page 70
Image 70
Analog Signalling Mode (2-state): menu level 0

Appendix A

Lower Threshold Setting (2-state mode)

The Lower Threshold Setting is the % of range below which the probe is considered uncovered. In order to switch the output signal, the corresponding delay time has to be met (Menu 04).

The loop-current control (Menu 07) must be in 2-state mode for this menu to display the Upper Threshold Setting in percent. As an extra identifier, a downward ramp Manual background is displayed to the right of the value.

Menu

Affected

Rotary

Left

 

 

Added

 

 

Switch

Mode

 

Description

Values

Item

by:

Position

Arrow

 

 

Indicator

 

 

 

 

 

 

 

 

Downward

Lower

% of

 

 

 

 

2-state

 

ramp at right

Threshold

 

 

 

 

 

range

 

 

 

 

 

 

of value

Setting

06

07

6

Off

 

 

 

 

 

 

 

 

 

 

 

 

Display

 

 

 

 

 

 

 

 

 

 

 

 

Analog

*

 

 

shows

 

 

 

 

 

 

 

 

- - - -

 

 

 

 

 

 

 

 

 

1.Set the loop-current control (Menu 07) to 2-state mode.

2.Set the rotary switch to 6.

3.Press the RED (+) or BLUE (–) button to increase or decrease the value. or: Press and hold a button to start a repeat function.

Analog Signalling Mode (2-state): menu level 0

Note: Menu 08 has precedence over the settings in Menu 07.

The factory setting is for Analog mode (the loop-current is proportional with the percentage of the range). When no buttons are pressed, the LCD displays the current mA value.

2-state Signalling Mode provides a 4 mA or 20 mA output. The settings are relative to a covered probe:

C: Hi selects a 20 mA signal for a covered probe, which switches to 4 mA if the probe becomes uncovered.

C: Lo selects a 4 mA signal for a covered probe, which switches to 20 mA if the probe becomes uncovered.

Page 64

SITRANS LC 500 – INSTRUCTION MANUAL

7ML19985GE01

Page 70
Image 70
Siemens LC 500 Analog Signalling Mode 2-state menu level, Appendix A, Menu, Affected, Description, Values, Position