Display shows nor

Range Inversion

Displays whether the device is operating with a normal or inverted range setting.

A normal range setting is where LRV (Menu 0E) is lower in value than URV (Menu 0F): the LCD displays nor. An inverted range is where LRV (Menu 0E) is higher in value than URV (Menu 0F): the LCD displays inv.

Menu

Rotary

 

 

 

 

 

Switch

Left Arrow

Description

Mode

Values

Item

Position

 

 

 

 

 

 

 

 

 

 

 

19

9

On

Range Inversion

normal

*

Display shows nor

 

 

 

inverted

 

Display shows inv

 

 

 

 

 

 

 

 

 

 

 

 

1.Set the rotary switch to 9.

2.Press both buttons simultaneously for more than one second to toggle between the two modes, effectively switching the values for LRV and URV.

Keylock Level

Controls the access protection level for the device. The factory setting is a local protection level of 0, which places no restriction on modifying settings locally.

Note: HART settings override local settings:

If the HART setting is 0, there are no restrictions, and you cannot change the protection to a higher level locally.

If the HART setting is 3, no changes can be made, and this protection level cannot be changed locally.

Protection level 1 disables the ability to set a value by pressing two buttons simultaneously.

Protection level 2 disables the ability to change a value by stepping it up or down.

Protection level 3 completely disables all changing of values.

Menu

Rotary

Left

 

Protection

Display

Switch

 

 

 

local

HART

Item

Arrow

Level

 

Description

Position

 

settings

settings

 

 

 

 

 

 

 

 

0

*

No restrictions

PL 0

 

 

 

 

 

 

 

 

 

 

 

 

No restrictions

 

PH 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

Disables 2-button

PL 1

PH 1

 

 

 

 

adjustments

1F

F

On

 

 

 

 

 

 

 

 

 

2

 

Disables 1-button

PL 2

PH 2

 

 

 

 

 

 

 

 

adjustments

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

Disables all

PL 3

PH 3

 

 

 

 

changes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Set the rotary switch to F.

2.Press the RED (+) or BLUE (–) button to change the setting.

Appendix A

7ML19985GE01

SITRANS LC 500 – INSTRUCTION MANUAL

Page 73

Page 79
Image 79